Appendix 5: Regulatory approvals
5.4 Aux loading and battery selection
HS3128/HS3032/
HS3248 PCB cur-
rent draw = 120
mA Alarm cur-
rent = 700 mA
UL Resi Burg
ULC Resi Burg
UL Com Burg
UL Resi Fire UL
Home Health
Care ULC Resi
Fire ULC Com
Burg
UL Resi Fire
with wired CO
Detectors
UL985 6th Ed
ULC COM Fire
Monitoring
EN50131
Grade 2
EN50131
Grade 3
Standby Time
and Alarm Time
4 h + 4 min
4 h + 5 min
4 h + 15 min
24 h + 4 min
24 h + 5 min
24 h + 4 min
24 h + 4 min +
12 h CO alarm
24 h + 30 min
12 h
30 h (AC fail
transmission
required)
60 h
Enclosure
HSC3010C
HSC3030CAR
HSC3010C
HSC3010C
HSC3010CR
HSC3020C HSC3020C
Power Supply
Adapter
HS65WPSNA
HS65WPSNA
HS65WPSNA
HS65WPSNAS
(ULC CB Security
Level 4) (Require
high voltage barrier
kit)
HS65WPSNA
HS65WPSNAS
HS65WPS
HS65WPS
Battery capacity
/max loading
4 Ah/700 mA
7 Ah/1200 mA
14 Ah/2000 mA
17 Ah/2000 mA
4 Ah/700 mA
7 Ah/1200 mA
14 Ah/2000 mA
17 Ah/2000 mA
7 Ah/250 mA
14 Ah/500 mA
17 Ah/600 mA
14 Ah/330 mA
17 Ah/400 mA
14 Ah/500 mA
17 Ah/600 mA
17 Ah/
1200 mA
17 Ah/500
mA
17 Ah/250
mA
Recharging cur-
rent setting
Low (400 mA) for
4 Ah/High (700
mA)
Low (400 mA) for
4Ah/High (700
mA)
High (700 mA)
High (700 mA)
High (700 mA)
Low
(400 mA)
High
(700mA)
Note:
For NFA2P 2 shield installations, use 18 Ah batteries and 450 mA load for 36-hour standby. For NFA2P 3 shield install-
ations, use 18 Ah batteries and the same loadings as for EN50131 Grade 3 in the table above.
5.5
SIA False Alarm Reduction Installations: Quick Reference
Minimum required system consists of one Control unit model HS3032, HS3128, or HS3248, and any one of the compatible
listed keypads (refer to
The following wireless keyfobs can also be used in SIA compatible installations: PG9929, PG9939,PG9949.
Note:
For models PG9929 and PG9939, the panic/emergency key shall be disabled for SIA compliant installations.
For a list of the default values programmed when the unit is shipped from the factory, and for other programming information,
refer to the following table.
The following optional subassembly modules also bear the SIA CP-01-2014 classification and may be used if desired:
HSM2108 zone expander, HSM2208 PGM output module, HSM2300 auxiliary power supply, HSM2204 output module,
HSM2HOST9 2-way wireless transceiver, PG9901 indoor siren, PG9911 outdoor siren, and LE9080/3G9080/3H9080 cel-
lular and PSDN communication module.
Caution
l
For SIA FAR installations use only modules/devices that are listed on this page.
l
Fire Alarm Verification feature (Auto Verified Fire Zone type [025]) is not supported on 2-wire smoke detectors zones,
model FSA-210B(T)(S)(ST)(LST)(R)(RT)(RD)(RST)(LRST). This feature may be enabled for 4-wire smoke detectors
only (FSA-410B(T)(S)(ST)(LST)(R)(RT)(RST)(LRST) and wireless detectors PG9916/PG9926). The fire alarm delay
is 60s.
l
Call Waiting Cancel (Section [382], option 4) on a non-Call Waiting line will prevent successful communication to the
supervising station.
l
All system smoke detectors must be tested annually by conducting an Installer Walk Test. Prior to exiting Walk Test
mode, a sensor reset must be done on the system, [*][7][2], to reset all latching 4-wire smoke detectors. Refer to the
installation instructions supplied with the detector for details.
- 270 -