Section 5: Programming
OFF: activated during normal operation. Deactivated when triggered.
184 – Open After Alarm
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: activated during normal operation. Deactivated when triggered.
200 - Zone Follower - Single Zone
01 – True Output/Inverted
ON: deactivated during normal operation, activated when triggered.
OFF: activated during normal operation, deactivated when triggered.
02 – Timed Output
ON: output remains active until the PGM output timer expires.
OFF: output remains active until the zone is restored.
04 – Latching
ON: output remains latched until a valid access code is entered or a valid Prox tag is presented.
OFF: output follows the setting of the Timed Output attribute.
05 – Follow Alarm
ON: output is activated on zone alarm and stays active until the bell is turned off. See table for operation with bits 2
and 4.
OFF: output is activated on zone opening and deactivated when zone is closed.
Timed Output Latching Follow Alarm PGM Output
OFF
OFF
OFF
ON upon zone opening (including tamper and fault), OFF upon zone closing
OFF
OFF
ON
ON upon zone alarm, OFF upon bell cut-off or alarm silenced
OFF
ON
OFF
ON upon zone opening, OFF upon valid code
OFF
ON
ON
ON upon zone alarm, OFF upon valid code
ON
OFF
OFF
ON upon zone opening, OFF upon PGM timer expires
ON
OFF
ON
ON upon zone alarm, OFF upon PGM timer expires
ON
ON
OFF
ON upon zone opening, OFF upon valid code
ON
ON
ON
ON upon zone alarm, OFF upon valid code
201 – 231 Zone Follower Zones 1-248
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: activated during normal operation. Deactivated when triggered.
02 – Timed Output
ON: output remains active until the PGM output timer expires.
OFF: output remains active until an access code has been entered.
09-16 – Zone Terminals 1-8
ON: zones associated with terminals 1-8 are enabled for zone follower operation.
OFF: zones are not enabled for zone follower operation.
[011] PGM Configuration Options
This section is used to configure PGM types that offer multiple options.
[001]-[324] Select PGM
The following options may be selected for each PGM:
- 100 -