Keypad Partition Setup
Keypads can be configured to control an individual partition or all partitions. In general, a partition
keypad controls the partition it is assigned to. A Global keypad controls all partitions. Global
keypads should be placed in common areas of the premises, such as points of entry or reception
areas, where the ability to arm and disarm more than one partition at a time is required. Partition
keypads can also be temporarily loaned to other partitions. To select a keypad operating mode:
1. Enter Installer Programming: [*][8][installer code].
2. Select [861]-[876] to program keypads 1-16.
- Press [000] for partition assignment.
- For Global operation, key in 00.
- To assign a keypad to a partition, key in 01-08 for partition 1-8.
3. Press the [#] and reapeat step 2 for next keypad. When finished programming all keypads,
press the [#] key twice to exit programming.
Users are assigned partition access rights via the [*][5] menu.
Loaned Partition Setup
To loan a keypad to another partition:
1. Press and hold [#] then key in a valid access code. The keypad switches to Global display.
2. Use the arrow keys to scroll through available partitions. Press [*] to select. The keypad is
temporarily loaned to another partition.
If the keypad is inactive for more than 30 seconds, it reverts to its assigned partition.
Global Zones
If a zone is added to more than one partition, it becomes a global zone. A global zone is only armed
when all assigned partitions are armed and is disarmed when any assigned partition is disarmed.
Global zones behave as follows:
• A global Stay/Away type zone is not activated until all partitions the zone is assigned to are
armed in the Away mode. Interiors must be activated on all partitions for the global Stay/Away
zone to be active.
• A shared zone bypassed on one partition is bypassed on all partitions the zone is assigned to.
• An entry delay started on a global zone sounds an entry delay on all keypads assigned to
partitions the global zone is assigned to.
• A global Delay type zone follows the longest programmed delay time of the partitions it is
assigned to.
Fire and CO Zone Types
• Fire zones only place the partition they are assigned to into alarm. Other partitions retain their
current state. A fire reset only resets assigned partitions.
• One or more fire zones may be located on any partition.
• On alarm, the fire auto-scroll display appears on all partition keypads and on all global
keypads. Fire alarm silence and fire system reset may be done directly on any partition keypad.