Johnson Controls FX-PCX3721 Installation Instructions Manual Download Page 13

Technical Specifications

Table 9: FX-PCX3721 Technical Specifications

FX-PCX3721 Expansion Input/Output Module

Product Code Number

24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply
Class 2 (North America), Safety Extra-Low Voltage (SELV) (Europe)

Supply Voltage

14 VA maximum

Power Consumption

Operating:

0 to 50°C (32 to 122°F); 10 to 90% RH noncondensing

Storage:

-40 to 80°C (-40 to 176°F); 5 to 95% RH noncondensing

Ambient Conditions

DIP switch set; valid controller device addresses 4–127 (Device addresses 0–3 and
128–255 are reserved and not valid controller addresses.)

Addressing

BACnet

®

MS/TP, RS-485:

3-wire FC Bus between the supervisory controller and other controllers

4-wire SA bus between controller, network sensors and other sensor/actuator devices,
includes a lead to source 15 VDC supply power (from controller) to bus devices.

Communications Bus

H8SX/166xR Renesas

®

32-bit microcontroller

Processor

640 KB Flash Memory and 128 KB Random Access Memory (RAM)

Memory

16 - Binary Inputs:

Defined as Dry Contact Maintained or Pulse Counter/Accumulator

Mode

Input and Output Capabilities

Input/Output:

Fixed Screw Terminal Blocks

SA/FC Bus and Supply Power:

4-Wire and 3-Wire Pluggable Screw Terminal

Blocks

SA/FC Bus Port:

RJ-12 6-Pin Modular Jacks

Terminations

Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface
with three integral mounting clips on controller

Mounting

Enclosure material:

ABS and polycarbonate UL94 5VB; Self-extinguishing, Plenum

Rated

Protection Class: IP20 (IEC529)

Housing

150 x 164 x 53 mm (5-7/8 x 6-1/2 x 2-1/8 in.) including terminals and mounting clips

Note:

Mounting space requires an additional 50 mm (2 in.) space on top, bottom

and front face of controller for easy cover removal, ventilation and wire terminations.

Dimensions(Height x Width x Depth)

0.5 kg (1.1 lb)

Weight

United States:

UL Listed, File E107041, CCN PAZX, UL 916, Energy Management

Equipment

FCC Compliant to CFR47, Part 15, Subpart B, Class A

Compliance

Canada:

UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No.205, Signal

Equipment

Industry Canada Compliant, ICES-003

Europe:

Johnson Controls, Inc. declares that this product is in compliance with the

essential requirements and other relevant provisions of the EMC Directive
2004/108/EC.

Australia and New Zealand

: C-Tick Mark, Australia/NZ Emissions Compliant

BACnet International:

BACnet Testing Laboratories (BTL) Protocol Revision 4

Listed BACnet Application Specific Controller (B-ASC)

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls

®

office. Johnson Controls, Inc. shall not be liable

for damages resulting from misapplication or misuse of its products.

13

FX-PCX3721 Expansion Input/Output Module Installation Instructions

Summary of Contents for FX-PCX3721

Page 1: ...es uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipmen...

Page 2: ...at the top of the DIN rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on...

Page 3: ...Removing the Controller Cover 3 Sensor Actuator SA Bus or Field Controller FC Bus Terminal Block See SA FC Bus Terminal Block 4 End of Line EOL Termination Switch See Setting the End of Line EOL Swit...

Page 4: ...c discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed information on configu...

Page 5: ...le 5 for more information The SA FC bus port pin assignment is shown in Figure 6 Figure 6 Pin Number Assignments for Sensor SA Bus and FC Bus Ports on Controllers Supply Power Terminal Block The 24 VA...

Page 6: ...nation diagrams provides details for wiring inputs and outputs to the controllers See Table 2 in this section for the applicable termination diagram Table 2 Termination Details Termination Diagrams Ty...

Page 7: ...Wire Size Gauge and Type Guideline 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or outpu...

Page 8: ...rve these guidelines when wiring an SA or FC bus and the 24 VAC supply power Run all low voltage wiring and cables separate from high voltage wiring All SA and FC bus cables regardless of wire size sh...

Page 9: ...ths for cables 2 The SA Bus and FC Bus wiring recommendations in this table are for MS TP bus communications at 38 400 baud For more information refer to the FX PC Series Controllers MS TP Communicati...

Page 10: ...P Communications Bus for BCM System Technical Bulletin LIT 12011908 for more information on controller device addresses and how to set them on MS TP buses Table 6 SA FC Bus Device Address Descriptions...

Page 11: ...switch set to ON the amber EOL LED on the controller cover is lit Commissioning the Controllers You commission controllers with the FX PCT software either via a Bluetooth Commissioning Converter a Zi...

Page 12: ...r more information Y65T31 0 Power transformer Class 2 24 VAC 50 VA maximum output no enclosure AS XFR050 0 Replacement SA Bus Terminal Blocks 4 Position Brown Bulk Pack AP TBK4SA 0 Replacement FC Bus...

Page 13: ...preferred or screw mount on flat surface with three integral mounting clips on controller Mounting Enclosure material ABS and polycarbonate UL94 5VB Self extinguishing Plenum Rated Protection Class IP...

Page 14: ...son Controls is a registered trademark of Johnson Controls Inc All other marks herein are the marks of their respective owners 2014 Johnson Controls Inc www johnsoncontrols com Published in U S A 14 F...

Reviews: