100.210-IOM (FEB 2015)
Page 66
VYPER
™
VARIABLE SPEED DRIVE
MAINTENANCE
be.generated..Check.to.see.that.the.serial.communications.
have.been.established.by.selecting.the.Motor.information.
screen.verifying.the.drive.horsepower..A.zero.displayed.
value.for.this.parameter.(and.all.other.Vyper
™
.parameters).
indicates.a.serial.communications.link.or.EPROM.problem.
•. If.the.harmonic.Filter.option.is.included,.make.sure.the.
harmonic. Filter. Logic. board. is. not. in. continuous. reset..
This.will.be.evidenced.by.the.LEDs.on.the.filter.logic.board.
alternately. blinking.. To. rule. out. the. harmonic. Filter. as.
the.cause.of.initialization.failure,.disconnect.the.filter.by.
switching.the.filter.logic.board’s.SW1.switch.to.the.OFF.
position,.and.removing.the.16.wire.ribbon.cable.between.
the.harmonic.Filter.logic.and.Vyper
™
.Logic.Board.
Fault 8: Vyper - Stop Contacts
Message
Quantum:.“Fault.8.“
Quantum.LX:.“VSD.Stop.Contacts.Fault.“
This.fault.occurs.if.the.No.Fault.signal.from.the.Vyper
™
..is.low..
It.indicates.a.fault.is.present.at.the.Vyper
™
.or.the.harmonic.
Filter,.but.the.communications.data.contains.no.Vyper
™
.fault.
data.for.twenty.seconds..The.Frick.Interface.Board.will.send.
Initialize.data.requests.while.this.fault.is.active.
Whenever.the.Vyper
™
.initiates.a.fault,.the.Vyper
™
.first.opens.
the. K1. relay. on. the. Vyper
™
. Logic. board.. When. the. relay.
opens,.the.voltage.between.wire.#53.and.#16.will.be.115.
VAC..I.f.wire.#53.to.#16.circuit.ever.opens.without.receiv-
ing.an.accompanying.cause.for.the.trip.over.the.serial.link.
(within.11.communication.tries,.approximately.22.seconds),.
this.Fault.Code.will.be.displayed..A.loose.wire.is.often.the.
cause.of.this.problem..Check.the.#1.to.#53.horseshoe.jumper.
in.the.Control.Center.and.all.other.wiring.involving.#53.and.
#16..This.fault.may.be.replaced.with.a.Serial.Communications.
fault.if.the.serial.link.has.failed..
Fault 9: Harmonic Filter - Logic Board Or Communications
Message
Quantum:.“Fault.9.“
Quantum.LX:.“harmonic.Filter.Logic.Board.or.Comms.Fault.“
This.fault.occurs.if.the.No.Fault.signal.from.the.Vyper™.is.low,.
indicating.a.fault.is.present.at.the.Vyper™.or.the.harmonic.
Filter,.but.the.communications.data.contains.no.harmonic.
Filter.fault.data.for.twenty.seconds..The.Frick.Interface.Board.
will.send.Initialize.data.requests.while.this.fault.is.active..
This.Fault.Code.can.also.occur.as.a.background.message.
when.the.chiller.is.running..When.this.message.is.displayed,.
all.filter.related.values.are.unavailable..If.communications.
is. reestablished,. normal. values. will. again. be. displayed.. If.
this. problem. is. encountered,. the. ribbon. cable. connecting.
the.Vyper™.Logic.board.to.the.Filter.Logic.board.should.be.
checked..The.integrity.of.the.shielded.communications.cable.
between.the.filter.logic.board.and.the.interface.board.should.
also.be.checked..Finally,.replacement.of.either.the.filter.logic.
board.or.the.Vyper™.Logic.board.should.be.tried.
Fault 10: Harmonic Filter - High Total Demand Distortion
Message
Quantum:.“Fault.10”
Quantum.LX:.“harmonic.Filter.high.Total.Demand.Distortion’’
This.shutdown.indicates.that.the.filter.is.not.operating.cor-
rectly. or. the. input. current. to. the. Vyper™/filter. system. is.
not.sinusoidal..This.fault.occurs.when.any.one.of.the.three.
phases. of. Total. Demand. Distortion. (TDD). is. greater. than.
25.0.%,.for.forty-five.continuous.seconds.while.the.Vyper™.
is.running..TDD.is.defined.by.the.IEEE.Std.519-1992.standard.
as.“the.total.root.-.sum.-.square.harmonic.current.distor-
tion,.in.percent.of.the.maximum.demand.load.current.(15.or.
30.min.demand)”..In.the.filter.option.supplied.by.Frick,.the.
displayed.TDD.is.the.total.RMS.value.of.the.harmonic.current.
supplied.by.the.power.mains.to.the.Vyper™.system.divided.
by.the.FLA.of.the.Vyper™,.in.percent..The.harmonic.filter.
option.was.designed.to.provide.an.input.current.TDD.level.
of.8%.or.less.for.the.Vyper™.system..A.standard.Vyper™.
less. the. optional. filter. typically. has. an. input. current. TDD.
level.on.the.order.of.28.-.30%..Causes.for.this.shutdown.
are.numerous,.but.would.most.likely.be.caused.by.a.faulty.
filter.logic.board..In.order.to.initiate.a.chiller.run.again,.the.
Quantum™LX.panel’s.compressor.switch.must.first.be.placed.
into.the.STOP/RESET.position.
Fault 11: High Phase B Inverter Baseplate Temperature
Message
Quantum:.“Fault.11”
Quantum.LX:.“high.Phase.B.Inverter.Baseplate.Temperature”
The.phase.bank.assembly.shall.contain.one.heat.sink.to.cool.
the.three.inverter.power.modules.and.the.converter.SCR/
Diode.modules..The.inverter.power.modules.each.contain.
an.internal.temperature.sensor.(5K.ohm.at.25°C).to.monitor.
their. baseplate. temperatures.. Each. of. the. inverter. power.
module.baseplate.temperatures.are.compared.in.software.
to.a.limit.of.175°F.(79°C)..If.this.limit.is.exceeded,.the.unit.
initiates.a.safety.shutdown..The.fan(s).and.water.pump.re-
main.energized.until.the.inverter.power.module.baseplate.
temperature.falls.below.165°F.(74°C)..The.fans.and.pumps.are.
de-energized.when.all.baseplate.temperatures.drop.below.
the.reset.thresholds.
Fault 12: High Phase C Inverter Baseplate Temperature
Message
Quantum:.“Fault.12”
Quantum.LX:.“high.Phase.C.Inverter.Baseplate.Temperature”
Same. comments. as. Fault. 11. except. applying. to. Phase. C.
Inverter.Baseplate.Temperature
Fault 13: Low Phase B Inverter Baseplate Temperature
Message
Quantum:.“Fault.13”
Quantum.LX:.“Low.Phase.B.Inverter.Baseplate.Temperature”
The.phase.bank.assembly.shall.contain.one.heat.sink.to.cool.
both.the.inverter.power.module.and.the.converter.SCR/Diode.
modules..The.three.inverter.power.modules.each.contain.
internal.temperature.sensors.(5K.ohm.at.25°C).to.monitor.
baseplate.temperature..The.inverter.power.module.baseplate.
temperatures.are.compared.in.software.to.a.lower.limit.of.
37°F.(2.8°C)..If.this.limit.is.exceeded,.the.unit.initiates.a.cy-
cling.shutdown..In.addition,.if.the.three.inverter.baseplates.
and.the.converter.heat.sink.temperature.falls.below.the.37°F.
limit,.the.unit.will.trip.and.energize.the.fan(s).and.coolant.
pump..This.feature.provides.service.personnel.with.a.means.
to.run.the.water.pump.while.filling.the.cooling.system.(by.
pulling.VSD.logic.board.plug.P2).
Fault 14: Low Phase C Inverter Baseplate Temperature
Message
Quantum:.“Fault.14”
Quantum.LX:.“Low.Phase.C.Inverter.Baseplate.Temperature”
Same. comments. as. Fault. 13. except. applying. to. Phase. C.
Inverter.Baseplate.Temperature