Setting up the derivative constant
1. To view PID settings, tap
PID Loop
.
2.
To find the PID loop setup you want to adjust the derivative gain for, swipe left.
3. On the
PID LOOP SETUP
screen, expand
Derivative
and move the slider to set the derivative gain. Set the derivative constant to
a default of zero for most applications.
4.
Optional:
Use the
Revert
icon to revert back to the previous setting.
5.
To confirm the settings, collapse
Derivative
.
PID constant
Default value
Proportional
20
Integral
5
Derivative
0
Table 7: PID default settings