FMS-2000C
LIT-12013504
41
Specifying the action mode for CO
2
control
The action mode determines the polarity of the output based on sensor input. To specify the action mode, complete the following steps:
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3.
To find the analog output you want to change the action mode for, swipe left.
4. On the
ANALOG
screen, tap
Output
.
5. To specify the action mode, tap the
Action Mode
arrow and tap
Direct
or
Reverse
.
6. Collapse
Action Mode
to save the new settings.
Selecting the corresponding analog input channel for CO
2
control
Map the corresponding analog input channel to the analog output channel.
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3.
To find the analog output you want to change the analog input channel for, swipe left.
4. On the
ANALOG
screen, tap
Output
.
5. To select a corresponding analog input channel for this analog output, tap the
Input Channel
arrow.
6. Scroll to the corresponding analog input channel and tap the
Checkmark
icon to confirm your settings.
Setting up limits for CO
2
control
Limits prevent the analog output from going beyond a predetermined voltage or current output. You can specify the minimum and
maximum limits for the analog output in percentage. The default minimum is zero and the default maximum is 100%.
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3.
To find the analog output you want to change the limit for, swipe left.
4. On the
ANALOG
screen, tap
Output
.
5. To set an upper and lower limit, tap the
Limit
arrow.
6. Move the sliders towards the
Plus
icon to increase or towards the
Minus
icon to decrease the
Upper
and
Lower
Limit.
7.
To confirm the new settings, tap the
Checkmark
icon.