FMS-2000C
LIT-12013504
27
Configuring the analog outputs to control pressure
If you are controlling pressure, configure the corresponding analog output to the analog input as required by the specific application.
Refer to the wiring diagrams in the submittal package and the
FMS-2000C Critical Environment Controller Installation Guide
(LIT-12013508)
to map the output correctly.
Specifying the operating mode
Each of the four analog outputs of the FMS-2000C controller can be configured for the following operating modes:
•
Direct operating mode
•
PID operating mode
In direct operating mode, the output tracks the mapped analog input directly or inversely. The PID operating mode may or may not
employ the proportional-integral-derivative scheme for closed-loop control of the analog output. The range of the output may or may not
include an offset. This is independent of the mode the analog output is configured to.
To change the operating mode, complete the following steps:
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3.
To find the analog output you want to change the operating mode for, swipe left.
4. On the
ANALOG
screen, tap
Output
.
5. To change the operating mode, expand the
Operating Mode
arrow and tap
Direct Analog
or
PID Analog
.
6. Collapse
Operating Mode
to save the new settings.
Specifying the output range
When you select the 0-5V, 0-10V, 0-20mA range, the analog output swings from zero to maximum specified by the hardware DIP switch
selection. The 1-5V, 2-10V, 4-20mA range includes an offset from zero. To specify the output range, complete the following steps:
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3.
To find the analog output you want to change, swipe left.
4. On the
ANALOG
screen, tap
Output
.
5. To specify the output range, expand
Range
.
6. To select a range, tap one of the following:
•
0-5V, 0-10V, 0-20mA
•
1-5V, 2-10V, 4-20mA
7. Collapse
Range
to save the new settings.
Specifying the action mode
The action mode determines the polarity of the output based on sensor input. The action mode can be used to invert the polarity of
the incoming analog signal when the pressure sensor has been installed outside of the monitored space. To specify the action mode,
complete the following steps:
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3.
To find the analog output you want to change the action mode for, swipe left.
4. On the
ANALOG
screen, tap
Output
.
5. To specify the action mode, tap the
Action Mode
arrow and tap
Direct
or
Reverse
.
6. Collapse
Action Mode
to save the new settings.
Mapping the corresponding analog input channel
Map the corresponding analog input channel to the analog output channel.
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view analog input settings, tap
Analog I/O
.
3.
To find the analog output you want to change, swipe left.
4. On the
ANALOG
screen, tap
Output
.
5. To select a corresponding analog input channel for this analog output, tap the
Input Channel
arrow.
6. Scroll to the corresponding analog input channel and tap the
Checkmark
icon to confirm your settings.
Setting up limits
Limits prevent the analog output from going beyond a predetermined voltage or current output. You can specify the minimum and
maximum limits for the analog output in percentage. The default minimum is zero and the default maximum is 100%.
1. On the home screen, tap the
Settings
icon to enter the
Settings
menu.
2. To view the Analog Input/Output settings, tap
Analog I/O
.
3. On the
Analog
screen, tap
Output
.
4.
To find the analog output you want to change the limit for,
swipe left.
5. To set an upper and lower limit, tap the
Limit
arrow.
6. Move the sliders towards the
Plus
icon to increase or towards the
Minus
icon to decrease the
Upper
Limit
.
7. Move the sliders towards the
Plus
icon to increase or towards the
Minus
icon to decrease the
Lower
Limit
.
8.
To confirm the new settings, tap the
Checkmark
icon.