Technical specifications
Specification
Description
Models
Non-programmable: FCP-NA-701-N, FCP-NA-701-B
Programmable: FCP-PA-701-N, FCP-PA-701-B
Power requirements
20 VAC to 30 VAC, 60 Hz, max. 3 A (3 VA at 24 V nominal)
Output rating
Valve and fan outputs 1 A maximum per each relay channel
(Max. relays ON combination: 3 relays), 20 VAC to 30 VAC
Analog inputs
Remote sensor
10K ohm at 77°F (25°C) NTC sensor
Pipe sensor
10K ohm at 77°F (25°C) NTC sensor
Set back
NC/NO dry contact switch
Local temperature sensor type
NTC temperature sensor, accurate to ±1°F (±0.6°C) at 77°F (25°C)
Remote temperature sensor type
NTC temperature sensor, accurate to ±2°F (±1.2°C) at 70°F (21°C)
Wire size
18 AWG (100 ft [30.5 m] maximum) to 24 AWG (36 ft [11 m] maximum)
Temperature adjustment range
Heat mode
45°F to 90°F (7°C to 32°C)
Cool mode
60°F to 95°F (15°C to 35°C)
Accuracy
Local temperature
sensor
±1°F (+/-0.6°C)
Remote temperature
sensor
±2°F (±1.2°C) at 70°F (21°C)
Remote pipe sensor
±5°F (±3.0°C)
Deadband
2°F to 5°F (1°C to 3°C)
Ambient conditions
Operating
14°F to 122°F (-10°C to 50°C); 5% RH to 90% RH, noncondensing
Storage
-4°F to 140°F (-20°C to 60°C); 5% RH to 90% RH, noncondensing
Disconnection means
Type 1B
Pollution degree
2
Rated impulse voltage
330 V
Automatic Action
100,000 cycles
Ratings for supply and loading
20 VAC to 30 VAC
Dimensions H x W x D
3.27 in. x 3.94 in. x 0.98 in. (83 mm x 100 mm x 25 mm)
Shipping weight
Product with packing and accessories: 10.1 oz (285 g)
Thermostat only: 4.9 oz (138 g)
Trim plate: 1.2 oz (33 g)
Compliance
ETL/cETL Listed, Mexico NOM
Conforms to UL STD. 60730-1 & 60730-2-9
Certified to CSA STD. E60730-1 & E60730-2-9
Table 8:
FCP technical specifications
Table 7: Common errors (part 2 of 2)
Error code Description
Solution
ER:12
ERROR_PIPE_
SENSOR_LO
Pipe sensor detected a too low temperature.
• Verify if the pipe sensor is installed correctly in the pipe.
• Contact technical support.