Network Room Module Technical Bulletin
29
Commissioning the NRM Module
To commission the NRM module:
1.
Check the network and power wiring to the NRM module.
2.
Turn on the module. If the power comes from the connected
FX controller, apply power to the controller.
On powerup, the NRM displays all symbols and segments of the
display while a self test is performed. If the NRM passes the self test,
the module begins to operate as configured with a display of space
temperature or setpoint and fan symbol (if supported). If the NRM
fails the self test, the display continues to show all symbols.
3.
Connect the FX CommPro N2, LON, or BACnet software tool to the
FX controller to monitor the NRM network variables through the
network profile as configured within the control application.
4.
Use the setpoint dial and fan push button to verify that the module is
operating and sending and receiving valid data from the controller.