Network Room Module Technical Bulletin
22
Commissioning the Network Room Module
General
The FX CommPro N2, LON, or BACnet commissioning tool is required
to commission the NRM room module and set up the parameters of the
module in the connected FX controller. The commissioning tool is
connected to the FX controller. You access the network variables and
configuration properties of the NRM through the network profile of the
FX controller application. Refer to the
FX Tools Software Package
FX Builder User Guide (LIT-12011154)
for details on how to build an
application and the corresponding network profile for either an N2, LON,
or BACnet MS/TP network (according to the network interface card
installed in the FX controller).
Temperature Sensor
During commissioning, if you find that the internal temperature sensor
does not read the exact value measured by a calibrated temperature
monitor, or you wish to compensate for a poorly located sensor, you can
adjust the space temperature value using the configuration property
Temperature Sensor Offset
. Do not use this parameter to compensate for
a faulty sensor in the NRM module. Replace the module if the reading is
more than a few degrees too high or low.