background image

Series DS-2 Dry-Type Sprinklers 

11.2K Pendent 

Extended Coverage, Light and Ordinary Hazard

Page 1 of 8 

FEBRUARY 2020 

TFP540

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

Series DS-2 Dry-Type Sprinklers must 

only be installed in fittings that meet 

the requirements of the Design Crite-

ria section.

Sprinkler 

Identification 

Number (SIN)

TY5238

Technical 

Data

Approvals

UL and C-UL Listed 

NYC Approved under MEA 173-02-E
See Table A. 

(These Approvals apply to the service 

condition indicated in the Design Criteria 

section.)

Maximum Working Pressure

175 psi (12,1 bar)

Inlet Thread Connections

1 in. NPT or 

ISO 7-R 1

Discharge Coefficient

See Table D

Temperature Ratings

See Table A

Finishes

Sprinkler: See Table E 

Escutcheon: See Table E

Physical Characteristics

Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Copper 

Yoke . . . . . . . . . . . . . . . . . . . . . . . Stainless Steel 

Casing  . . . . . . . . . . . . . Galvanized Carbon Steel 

Insert . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze 

Bulb Seat . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze 

Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass 

Compression Screw . . . . . . . . . . . . . . . . .Bronze 

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze 

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze 

Guide Tube . . . . . . . . . . . . . . . . .  Stainless Steel 

Water Tube  . . . . . . . . . . . . . . . . .  Stainless Steel 

Spring  . . . . . . . . . . . . . . . . . . . . . Stainless Steel 

Plug  . . . . . . . . . . . . . . . Copper Gasketed Spring

Plate Seal   . . . . . . . .Beryllium Nickel w/TEFLON 

Pin  . . . . . . . . . . . . . . . . . . . . . . . . Stainless Steel 

Button Spring . . . . . . . . . . . . . . .  Stainless Steel 

Escutcheon . . . . . . . . . . . . . . . . . . .Carbon Steel

General 

Description

TYCO Series DS-2 Dry-Type Sprinklers, 

11.2K Pendent, Extended Coverage, 

Light and Ordinary Hazard (ECLH/

ECOH) are decorative glass bulb auto-

matic sprinklers typically used where:
•  pendent sprinklers are required on 

dry pipe systems that are exposed 

to freezing temperatures (for exam-

ple, sprinkler drops from unheated 

portions of buildings)

•  sprinklers and/or a portion of the 

connecting piping may be exposed 

to freezing temperatures (for exam-

ple, sprinkler drops from wet sys-

tems into freezers)

NOTICE

Series DS-2 Dry-Type Sprinklers 

described herein must be installed 

and maintained in compliance with this 

document, as well as with the applica-

ble standards of the NATIONAL FIRE 

PROTECTION ASSOCIATION (NFPA), 

in addition to the standards of any other 

authorities having jurisdiction. Failure 

to do so may impair the performance 

of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Operation

When TYCO Series DS-2 Dry-Type 

Sprinklers, 11.2K Pendent, Extended 

Coverage, Light and Ordinary Hazard 

are in service, water is prevented from 

entering the assembly by the Plug 

with Gasketed Spring Plate Seal (see  

Figure 1) in the Inlet of the sprinkler.
The glass bulb contains a fluid that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter 

the glass bulb, and the Bulb Seat is 

released.
The compressed Spring is then able 

to expand and push the Water Tube as 

well as the Guide Tube outward. This 

action simultaneously pulls inward on 

the Yoke, withdrawing the Plug with 

Gasketed Spring Plate Seal from the 

Inlet allowing the sprinkler to activate 

and flow water.

Summary of Contents for DS-2 Series

Page 1: ...Carbon Steel General Description TYCO Series DS 2 Dry Type Sprinklers 11 2K Pendent Extended Coverage Light and Ordinary Hazard ECLH ECOH are decorative glass bulb auto matic sprinklers typically used where pendent sprinklers are required on dry pipe systems that are exposed to freezing temperatures for exam ple sprinkler drops from unheated portions of buildings sprinklers and or a portion of the...

Page 2: ... Figure 3 SPRINKLER FINISH Natural Brass Chromed Plated Polyester Natural Brass Chrome Plated Polyester 135 F 57 C Orange 1 2 3 1 2 3 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue Notes 1 UL Listed maximum order length of 48 in 2 C UL Listed maximum order length of 48 in 3 Approved by the City of New York under MEA 173 02 E 286 F 141 C temperature rating applies to installatio...

Page 3: ...20 F 29 C 14 355 6 150 3 75 30 F 34 C 16 405 8 200 4 100 40 F 40 C 18 455 8 200 4 100 50 F 46 C 20 510 10 255 6 150 60 F 51 C 20 510 10 255 6 150 Notes 1 For protected area temperatures that occur between values listed above use the next cooler temperature 2 These lengths are inclusive of wind velocities up to 30 mph 18 6 kph Response Rating Coverage Area 4 ft x ft m x m Minimum Flow 1 Light Hazar...

Page 4: ...gure 3 plus 1 4 in 6 3 mm Extended Order Length from Figure 4 plus 3 1 4 in 82 6 mm Without Escutcheon Order Length from Figure 5 minus 2 1 4 in 57 2 mm 2 1 4 1 8 57 2 3 2 mm ORDER LENGTHS 3 to 48 76 2 to 1219 2 mm IN 1 4 6 4 mm INCREMENTS ESCUTCHEON WILL PERMIT 1 4 6 4 mm ADJUSTMENT FACE OF SPRINKLER FITTING FACE OF CEILING 2 3 4 DIA 69 9 mm 3 5 8 DIA 92 1 mm SPRINKLER FITTING REFER TO DESIGN CRI...

Page 5: ...5 8 15 9 mm ADJUSTMENT FACE OF SPRINKLER FITTING FACE OF CEILING FOR ORDER LENGTHS 3 1 4 82 6 mm 4 7 8 1 8 123 8 3 2 mm or FOR ORDER LENGTHS 3 1 4 82 6 mm 5 5 8 1 8 142 9 3 2 mm 2 3 4 DIA 69 9 mm 3 5 8 DIA 92 1 mm ORDER LENGTHS 1 to 45 1 4 25 4 to 1149 4 mm IN 1 4 6 4 mm INCREMENTS SPRINKLER FITTING REFER TO DESIGN CRITERIA SECTION DO NOT FIGURE 4 SERIES DS 2 DRY TYPE PENDENT SPRINKLER ECLH ECOH W...

Page 6: ...or protected area temperatures between those given above the minimum recommended length from the face of the fitting to the outside of the protected area may be determined by interpolating between the indicated values You can also install Series DS 2 Dry Type Sprinklers in the 1 in NPT outlet of a GRINNELL Figure 730 Mechanical Tee However the use of the Figure 730 Tee for this arrangement is limi...

Page 7: ...s easier when a non hardening sealant was used and torque guidelines were followed After removal inspect the sprinkler for damage Step 3 After installing the ceiling and applying a ceiling finish slide on the outer piece of the Escutcheon until it comes in contact with the ceiling Do not lift the ceiling panel out of its normal position When using the Deep Escutcheon hold the outer piece in contac...

Page 8: ... applicable Part Number from Table E Sprinkler Wrench Specify W Type 17 Sprinkler Wrench P N 56 010 4 118 Sprinkler Boot Specify Model DSB 2 Dry Sprinkler Boot P N 63 000 0 002 This P N includes one 1 Boot two 2 Strap Ties and 1 3 oz of Adhesive a sufficient quantity for installing one boot Notes 1 Escutcheon Finish applies to sprinklers with escutcheons 2 286 F 141 C temperature rating applies to...

Reviews: