WARNING
Safety guards, shields, barrier, covers, and protective devices must not be removed while the
compressor/unit is operating.
WARNING
All safety features, disengagement and interlocks must be in place and function correctly before the
equipment is put into operation. Never bypass or wire around any safety device.
WARNING
Use gloves, protective goggles, and where appropriate, make sure to have a gas mask close at hand.
Also use electrical protection equipment and tools suited for electrical operation purposes.
Location
To ensure unit operates at maximum efficiencies, choose a dry indoor area where the temperature
is controlled between 50.0 °F and 115.0 °F. Consideration of surrounding areas should be taken
when choosing a location to install the unit. Common vibration and sound levels associated with
commercial equipment may be objectionable to people or equipment.
CAUTION
Failure to allow adequate space between units may result in poor unit performance and possible unit
failure.
Install thermostats, air supplies, and returns so that each unit will operate only on individual unit
control. To assure fast drainage of condensate run-off, unit can be slightly pitched in the same
direction as drain pan outlet.
Table 1: CSV operating weight (lbs)
Unit
Operating weight (condenser only)
Shipping weight (condenser only)
CSV060B
590
635
CSV096B
795
835
CSV120B
955
995
CSV180B
1310
1365
CSV240B
1465
1525
CSV300B
1930 (780)
2265 (980)
11
C-Series Vertical (CSV) Water-Cooled Self-Contained Units, B Generation, R-410A Installation, Operation, and
Maintenance Manual