Johnson Controls ASG-TP50RS Installation Manual Download Page 1

 

Model:  ASG-TP50RS

Installation Manual for Snow Protection Hood (for Outdoor Unit)

This snow protection hood prevents snow from entering the outdoor unit and prevents strong winds  from 
blowing against the heat exchanger. Be sure to read this manual carefully for correct performance before 
installation work.

 

  :  Indicates a hazardous situation that, if not avoided, 

 

  could result in death or serious injury.

 

  :  Indicates a hazardous situation that, if not avoided, 

 

  could result in minor or moderate injury.

1.  Applicable Unit

NOTICE: 

7KHDSSOLFDEOHRXWGRRUXQLWPD\EHGLႇHUHQWGHSHQGLQJRQWKHSURGXFWVHULHV%HVXUHWRFRQ¿UPZLWKWKH

product catalogue before installation.

Name

Hood for Side Air Inlet

Model

ASG-TP50RS

Applicable Outdoor Unit
(Representative Model)

(H,Y)VAH(P,R)072 - 192B32S
(H,Y)VAH(P,R)072 - 192B42S
(H,Y)VAH(P,R)072 - 192B52S

IMPORTANT NOTICE:

•  Johnson Controls-Hitachi Air Conditioning pursues a policy of continuous improvement in design and 

performance of products. 

:HUHVHUYHWKHULJKWWRYDU\VSHFL¿FDWLRQVZLWKRXWQRWLFH

•  Johnson Controls-Hitachi Air Conditioning cannot anticipate every possible circumstance that might involve 

a potential hazard.

•  No part of this manual may be reproduced without Johnson Controls-Hitachi Air Conditioning’ written 

permission.

•  Keep this manual for future reference.
•  Do not use this kit by itself or in combination with other companies’ air conditioners. This kit is designed for 

a combination of Johnson Controls-Hitachi Air Conditioning air conditioners only.

• 

8VHWKH¿HOGVXSSOLHGVDIHW\ZLUHURSHWRSUHYHQWRXWGRRUXQLWIURPRYHUWXUQLQJ8VHDVWD\RUVDIHW\ZLUH

rope to hold the snow protection hood properly to the outdoor unit against a strong wind or earthquake, for 
reinforced installation. 

•  Perform a test run after installation to check for abnormalities.
• 

8VHVLJQDOZRUGVWRLGHQWLI\OHYHOVRIKD]DUGVHULRXVQHVV'H¿QLWLRQVIRULGHQWLI\LQJKD]DUGOHYHOVDUH

provided below with their respective signal words.

2.  Installation Work

(1)  After the snow protection hood is installed, noise at the air outlet side may slightly increase. Consider 

carefully the air discharge direction when installing.

(2)  Tighten the snow protection hood securely to the top panel and side panel of the outdoor unit with the 

supplied screws (accessories). Not doing so may cause vibration or abnormal noise.

(3)  Avoid obstacles in the direction of air discharge from the snow protection hood to prevent short circuit 

RUDUHGXFWLRQLQWKHDLUÀRZUDWH

(4)  Do not install other outdoor units in the direction of the air outlet. If the air blown out of the snow 

protection hood is sucked into the other outdoor unit, it may cause a malfunction of the unit.

(5)  Double-check the strength of the anchor bolts of the outdoor unit. The wind loads on the outdoor unit 

change by attaching the snow protection hood. The required installation strength also changes in 
strong wind. 

 $IWHULQVWDOOLQJWKHVQRZSURWHFWLRQKRRGFRROLQJKHDWLQJSHUIRUPDQFHPD\EHVOLJKWO\DႇHFWHG

depending on usage.

1