Model: ASG-TP50BAS
ASG-TP50BBS
This snow protection hood prevents snow from entering the outdoor unit and prevents strong winds from
blowing against the heat exchanger. Be sure to read this manual carefully for correct performance before
installation work.
Installation Manual for Snow Protection Hood (for Outdoor Unit)
: Indicates a hazardous situation that, if not avoided,
could result in death or serious injury.
: Indicates a hazardous situation that, if not avoided,
could result in minor or moderate injury.
1. Applicable Unit
Name
Hood for Rear Side Air Inlet
Model
ASG-TP50BAS
ASG-TP50BBS
Applicable Outdoor Unit
(Representative Model)
(H,Y)VAH(P,R)072B32S
(H,Y)VAH(P,R)072B42S
(H,Y)VAH(P,R)072B52S
(H,Y)VAH(P,R)096 - 144B32S
(H,Y)VAH(P,R)096 - 144B42S
(H,Y)VAH(P,R)096 - 144B52S
NOTICE:
7KHDSSOLFDEOHRXWGRRUXQLWPD\EHGLႇHUHQWGHSHQGLQJRQWKHSURGXFWVHULHV%HVXUHWRFRQ¿UPZLWKWKH
product catalogue before installation.
2. Installation Work
(1) After the snow protection hood is installed, noise at the air outlet side may slightly increase. Consider
carefully the air discharge direction when installing.
(2) Tighten the snow protection hood securely to the top panel and side panel of the outdoor unit with the
supplied screws (accessories). Not doing so may cause vibration or abnormal noise.
(3) Avoid obstacles in the direction of air discharge from the snow protection hood to prevent short circuit
RUDUHGXFWLRQLQWKHDLUÀRZUDWH
(4) Do not install other outdoor units in the direction of the air outlet. If the air blown out of the snow
protection hood is sucked into the other outdoor unit, it may cause a malfunction of the unit.
(5) Double-check the strength of the anchor bolts of the outdoor unit. The wind loads on the outdoor unit
change by attaching the snow protection hood. The required installation strength also changes in
strong wind.
$IWHULQVWDOOLQJWKHVQRZSURWHFWLRQKRRGFRROLQJKHDWLQJSHUIRUPDQFHPD\EHVOLJKWO\DႇHFWHG
depending on usage.
IMPORTANT NOTICE:
• Johnson Controls-Hitachi Air Conditioning pursues a policy of continuous improvement in design and
performance of products.
:HUHVHUYHWKHULJKWWRYDU\VSHFL¿FDWLRQVZLWKRXWQRWLFH
• Johnson Controls-Hitachi Air Conditioning cannot anticipate every possible circumstance that might involve
a potential hazard.
• No part of this manual may be reproduced without Johnson Controls-Hitachi Air Conditioning’ written
permission.
• Keep this manual for future reference.
• Do not use this kit by itself or in combination with other companies’ air conditioners. This kit is designed for
a combination of Johnson Controls-Hitachi Air Conditioning air conditioners only.
•
8VHWKH¿HOGVXSSOLHGVDIHW\ZLUHURSHWRSUHYHQWRXWGRRUXQLWIURPRYHUWXUQLQJ8VHDVWD\RUVDIHW\ZLUH
rope to hold the snow protection hood properly to the outdoor unit against a strong wind or earthquake, for
reinforced installation.
• Perform a test run after installation to check for abnormalities.
•
8VHVLJQDOZRUGVWRLGHQWLI\OHYHOVRIKD]DUGVHULRXVQHVV'H¿QLWLRQVIRULGHQWLI\LQJKD]DUGOHYHOVDUH
provided below with their respective signal words.
1