![Johnson Controls AD-1252 Installation Instructions Manual Download Page 5](http://html.mh-extra.com/html/johnson-controls/ad-1252/ad-1252_installation-instructions-manual_2024328005.webp)
AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions
5
Oval Duct Mounting
Table 3: Number of Probes/Sensors per Probe for Oval Duct Applications
Duct
Height, in.
(A)
Duct Width, in.
(B)
12
18
24
36
42
48
60
72
96
120
12
2/2
2/2
1/3
1/3
3/2
3/2
4/2
4/2
4/2
4/2
18
2/2
1/3
1/3
3/2
3/2
4/2
2/4
2/4
2/4
24
2/2
2/3
3/2
3/2
4/2
2/4
2/4
2/4
36
2/4
3/3
3/3
4/3
2/4
2/4
2/4
42
2/4
3/3
4/4
4/4
4/4
4/4
48
3/4
4/4
4/4
4/4
4/4
60
4/4
4/4
4/4
4/4
72
4/4
4/4
4/4
96
4/4
4/4
120
4/4
Figure 5: Oval Duct Mounting - Sensor Density Details