This sensor must be installed in compliance with the control panel system installation manual. The installation must meet the requirements of the Authority 
Having Jurisdiction (AHJ). Sensors offer maximum performance when installed in compliance with the National Fire Protection Association (NFPA); see NFPA 
72.. 

GENERAL DESCRIPTION

Model 7351J is a plug-in type smoke sensor that uses a laser based photoelectronic sensing chamber. The sensor uses analog-addressable communications 

to transmit smoke density and other information to the control panel.
Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory (Part No. 
RA400Z).
Johnson Controls panels offer different features sets across different models. As a result, certain features of the product may be available on some control 

panels, but not on others. The possible features available in the product, if supported by the control unit are:
1. The panel controls the LED operation on the sensor. Operational modes are RED blink, RED continuous, GREEN blink, and off.
2. The remote output may be synchronized to the LED operation or controlled independent of the LEDs.
Please refer to the operation manual for the UL listed control unit for specific operation of the 7351J.

SPECIFICATIONS
Operating Voltage  
Range: 

15 to 32 VDC

Standby Current: 

330µA @ 24 VDC (one 

 

communication every 5 seconds

 

with LED blink enabled)

Max. Alarm Current (LED on):  6.5 mA @ 24 VDC
Operating Humidity Range: 

10% to 93% Relative Humidity,

 

noncondensing

Operating Temperature Range:  0°C to 38°C (32°F to 100°F); U.S.
 

–10°C to 50°C (14°F to 122°F); 

 

Europe

Height: 

1.7 inches (43 mm) installed

 

in B210LPJ Base

Diameter: 

6.1 inches (155 mm) installed

 

in B210LPJ Base

 

4.1 inches (104 mm) installed

 

in B501J Base

Weight: 

5.0 oz. (142 g)

SPACING
Johnson Controls recommends spacing sensors in compliance with NFPA 72. In low air flow applica-
tions  with  smooth  ceilings,  space  sensors  30  feet  apart.  For  specific  information  regarding  sensor 
spacing, placement, and special applications, refer to NFPA 72 or Johnson Controls 

System Smoke 

Detector Application Guide

, available at no charge from Johnson Controls.

WIRING INSTRUCTIONS
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, 
and  any  special  requirements  of  the Authority  Having  Jurisdiction.  Proper  wire  gauges  should  be 
used. The installation wires should be color-coded to limit wiring mistakes and ease system trouble-
shooting. Improper connections will prevent a system from responding properly in the event of a fire.
Disconnect power from the communication line before installing sensors.
All wiring must conform to applicable local codes, ordinances, and regulations.
1.  Wire the sensor base (supplied separately) per the wiring diagram (Figure 1).
2.  Set the desired address on the sensor address switches.
 

NOTE: Some panels support extended addressing. In order to set the sensor above address 99  
on  compatible  systems,  carefully  remove  the  stop  on  the  upper  rotary  switch  with  thumb  as 
shown in Figure 2.

3.  Install the sensor into the sensor base. Push the sensor into the base while turning it clockwise 

to secure it in place.

4.  After all sensors have been installed, apply power to the control unit and activate the commu- 

nication line.

5.  Test the sensor(s) as described in the 

TESTING section of this manual.

CAUTION

Dust covers provide limited protection against airborne dust particles during shipping. Dust covers 
must be removed before the sensors can sense smoke. Remove sensors prior to heavy remodeling 
or construction.

3

2

1

3

2

1

+

-

-

+

+

-

REMOTE 

ANNUNCIATOR

UL

 LISTED COM

P

A

TIBLE 

CONTROL

 P

ANEL

OPTIONAL RETURN LOOP

DO NOT LOOP WIRE 

UNDER TERMINAL 1 OR 2. 

BREAK WIRE RUN TO 

PROVIDE SUPERVISION 

OF CONNECTION.

C0147-00

Figure 1. Wiring Diagram

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

D

N

T

N

I

A P

T

O

O

LED STATUS

INDICATORS

TES

T

MAGNET

PAINTED

SURFACE

PAINTED

SURFACE

TEST

MAGNET

MAGNET TEST

MARKER

C0413-00

Figure 3.

Do not loop wire under terminal 
1  or  2.  Break  wire  to  provide 
supervision of connection.

CAUTION

Figure 2. Rotary Address Switches

7351J Intelligent Laser Smoke Sensor

Installation and Maintenance Instructions

C0162-00

I56-1898-003R