Installation and Maintenance Instructions for

5951J, 5951RJ and 5951HJ Intelligent Plug-in Temperature Sensors

This sensor must be installed in compliance with the control panel system installation manual. The installation must 
meet the requirements of the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when installed 
in compliance with the National Fire Protection Association (NFPA); see NFPA 72.

Before  installing  sensors,    please  read  the  system  wiring  and  installation  manual  thoroughly.  This  manual  provides 
detailed  information  on  sensor  spacing,  placement,  zoning,  and  special  applications.  Copies  of  these  manuals  are 
available from Johnson Controls.

GENERAL DESCRIPTION

Models 5951J, 5951RJ and 5951HJ are intelligent sensors that use a state-of-the-art thermistor sensing circuit for fast 
response. These sensors are designed to provide open area protection with 50 foot spacing capability. Model 5951J is 
a fixed temperature sensor with 135° F fixed temperature alarm. Model 5951RJ is a rate-of-rise temperature sensor with 
135° F fixed temperature alarm. Model 5951HJ is a high temperature sensor with 190° F fixed temperature alarm.
Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is avail-
able as an optional accessory (Part No. RA400Z).
Johnson Controls panels offer different feature sets across different models. As a result, certain features of the 5951J, 
5951RJ  and  5951HJ  may  be  available  on  some  control  panels,  but  not  on  others.  The  sensor  will  support  either 
FlashScan

 or CLIP (Classic Loop Interface Protocol) SLC Communication mode. The possible features available in 

the 5951J, 5951RJ and 5951HJ if supported by the control unit include:
1. The panel controls the LED operation on the sensor. Operational modes are RED blink, RED continuous, GREEN 
blink, GREEN continuous, and off.
2. The remote output may be synchronized to the LED operation or controlled independent of the LEDs.
Please refer to the operation manual for the UL listed control unit for specific operation of these models.

Models 5951J, 5951RJ and 5951HJ require compatible addressable SLC communications to function properly. 
Connect these sensors to listed-compatible control panels only.

SPECIFICATIONS

Diameter:                                             6.1 inches (155 mm) installed in B210LPJ                                                          
                                                             4.1 inches (104 mm) installed in B501J
Height:                                                  2.0 inches (51 mm) installed in B210LPJ or B501J bases
Weight:                                                 4.8 ounces (137 gm)
Installation Temperature
   5951J and 5951RJ:                           –4°F to 100°F (–20°C to 38°C)
   5951HJ:                                             –4°F to 150°F (–20°C to 66°C) 

 

 

Operating Humidity Range:                 10% to 93% Relative Humidity Noncondensing
Mounting:                                             B210LPJ flanged base
                                                             B501J flangeless base
Voltage Range:                                    15 to 32 Volts DC Peak
Standby Current:                                  300 

µ

A @ 24 VDC (one communication every 5 sec.with LED blink enabled)

LED Current:                                        6.5 mA @ 24 VDC
Fixed Temperature Setpoint
   5951J and 5951RJ:                           135°F (57°C)
   5951HJ:                                             190°F (88°C)
Rate of Rise Detection (5951RJ):        Responds to greater than 15°F/min.

Summary of Contents for 5951J

Page 1: ...ohnson Controls panels offer different feature sets across different models As a result certain features of the 5951J 5951RJ and 5951HJ may be available on some control panels but not on others The sensor will support either FlashScan or CLIP Classic Loop Interface Protocol SLC Communication mode The possible features available in the 5951J 5951RJ and 5951HJ if supported by the control unit includ...

Page 2: ... in place 4 After all sensors have been installed apply power to the control unit and activate the communication line 5 Test the sensor s as described in the TESTING section of this manual TAMPER RESISTANCE The sensor base includes a tamper proof feature which when activated prevents removal of the sensor without the use of a tool See the installation instruction manual for the sensor base for det...

Page 3: ...or base 3 Reset the detector at the system control panel Detectors that fail these tests should be cleaned as described under MAINTENANCE and retested If the detectors still fail these tests they should be returned for repair LED TEST MAGNET MARKER LED TEST MAGNET MARKER Figure 3 Views showing position of test magnet MAINTENANCE NOTE Before cleaning notify the proper authorities that the system is...

Page 4: ... radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is ...

Reviews: