Part No. 24-11443-00006, Rev. B

1

NS8000 Series

Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors

Graphical Display models

Part No. 24-11443-00006, Rev. B

Issue Date January 2020

Installation Guide

*241144300006RevB*

Important (USA, Canada)

The NS Series Network Sensor is intended to provide an input to equipment under normal operating conditions. Where failure or 

malfunction of the network sensor could lead to personal injury or property damage to the controlled equipment or other property, 

additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or 

alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the network sensor.

Le NS Series Network Sensor est destiné à transmettre des données entrantes à un équipement dans des conditions normales 

de fonctionnement. Lorsqu’une défaillance ou un dysfonctionnement du network sensor risque de provoquer des blessures ou 

d’endommager l’équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs 

de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d’autres dispositifs, tels que des systèmes de 

supervision ou d’alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d’avertissement ou de protection en 

cas de défaillance ou de dysfonctionnement du network sensor.

Mounting

466

72.0

74.5

40

CO2

°F

 466

ppm

72

CO2

40 

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC 

Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated 

in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed 

and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of 

this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the 

interference at their own expense.

Canada

This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations. 

Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

• 

You can surface mount or wallbox mount the NS Series Network Sensor. For wallbox-mounted installations, mount the 

NS Series Network Sensor on a vertically roughed-in wallbox only. Do not attempt to mount the sensor on a horizontally 

roughed-in wallbox.

• 

Johnson Controls® does not supply the required hardware to mount the sensors.  

Note:

Summary of Contents for 24-11443-00006

Page 1: ...es dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du network sensor Mounting 466 72 0 74 5 40 CO2 F 466 ppm 72 CO2 40 North American Emissions Compliance United States This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These l...

Page 2: ...Note Locate the network sensor away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference Height requirements may vary depending on the site Network sensors without CO2 sensing are shock and vibration resistant but not shock and vibration proof Be careful not to drop the unit or mount it where it could be exposed to excessive vibra...

Page 3: ...adhere to these wiring details causes the network sensor to function incorrectly You will not be able to connect to the system using the Bluetooth Wireless Comissioning Converter BTCVT Mobile Access Portal Gateway MAP or the handheld VAV balancing tool and you will not be able to expand the system with future offerings IMPORTANT Do not connect the SA bus ground the modular phone jack GND or the sc...

Page 4: ...Part No 24 11443 00006 Rev B 4 NS8000 Series 5 2 1 4 SA SA COM 15 VDC 15 VDC COM 15 VDC 1 2 5 6 4 3 COM SA SA 3 ...

Page 5: ...e setpoint temperature Network Network connection to host controller over SA bus No No network Sensor not connected to host controller No Settings Settings menu Settings lock Lockout mode Temperature Displays current temperature No Setting enabled Toggle setting is blue Setting disabled Toggle setting is white Error Title 24 error indicator Page indicator Settings screen page indicator Scroll arro...

Page 6: ... temperature relative humidity RH or CO2 show below the relevant icon Any interaction with a display screen activates temporary occupancy mode for 2 minutes See Figure 1 to 3 for individual graphical display screens Main screens overview Viewing the settings screens 1 Tap the Settings icon to access the settings screens 2 Tap the left and right arrows at the top of the screen to scroll through the...

Page 7: ...s icon and use the scroll arrow to navigate to the second page 2 To change the temperature unit tap the Toggle icon to switch between Fahrenheit and Celsius Title 24 error indicators In the event of a Title 24 related error the graphical screen displays the Error icon in the upper left of the display screen with the corresponding error code number for all the required state of California Title 24 ...

Page 8: ...curacy of the CO2 concentration measurement is essential modify the offset property of the NS Series CO2 Network Sensors Zone Quality ZN Q Analog Input AI The offset represents the local atmospheric pressure in hectopascals hPa Set the offset to the known local pressure or use the local altitude value listed in Table 3 The factory default value is 978 hPa As of Release 5 3 of the Controller Config...

Page 9: ...e measurement range 32 0 F 0 C to 104 F 40 C Temperature sensor type Digital temperature sensor Humidity sensor type Thin film capacitive sensor Ambient conditions Operating 32 F to 122 F 0 C to 50 C 10 to 90 RH noncondensing 85 F 29 C maximum dew point Storage 40 F to 122 F 40 C to 50 C 5 to 95 RH noncondensing Temperature resolution 0 5 F 0 5 C Temperature accuracy NS Series Network Zone Sensor ...

Page 10: ...ontact Johnson Controls www johnsoncontrols com contact us APAC JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA Europe JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY NA SA JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA Single point of contact The performance specifications are nominal and conform to acceptable indu...

Reviews: