JOHNSON CONTROLS
67
SECTION 5 – SEQUENCE OF OPERATION
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
5
• Unocc zone cooling setpoint must be set in the
SETPOINTS-COOLING menu if utilizing night
set-back.
• RAT heating setpoint must be set in the SET-
POINTS-HEATING menu (if applicable).
• Heating SAT setpoints must be set in the SET-
POINTS-HEATING menu (if applicable).
• Unocc zone heating setpoint must be set in the
SETPOINTS-HEATING menu if utilizing night
set-back.
• The IPU board must have a valid zone tempera-
ture reading if utilizing night set-back:
• Hardwired zone sensor to CTB1
• Communicated zone temperature from the
BAS
Supply Fan
• The supply fan must be running before any other
unit operation is allowed.
• The IPU board monitors the status of an APS to
determine the supply fan status.
•
When a VAV configured unit is in the Occ mode,
the supply fan is ON.
• The supply fan is cycled ON/OFF with a cooling/
heating demand on a VAV configured unit when in
the Unocc mode.
• The IPU board provides a start/stop signal to the
supply fan VFD.
• The IPU board outputs a 0–10 VDC signal to the
supply fan VFD to control the speed.
• The supply fan speed is controlled to achieve and
maintain the active duct static pressure setpoint.
Supply Fan Status
• The Series 100 units use an APS to determine sup-
ply fan status.
• The APS is a diaphragm type switch that closes at
approximately 0.30 iwg.
• The APS is mounted above the supply fan blower
assembly.
• The APS senses the static pressure through a fac-
tory installed tube that passes through the supply
fan wall into the next section of the unit.
• The APS needs to close and prove supply fan sta-
tus within 45 seconds after the supply fan is com-
manded on.
• Failure to prove supply fan status within 45
seconds causes a Supply Fan Lockout to occur.
• A Supply Fan Lockout also occurs if the APS
opens for more than 2 seconds once fan status is
proven to be RUNNING.
TABLE 24 -
VAV SUPPLY FAN SPEED
UNIT MODE
STATUS
Occ Standby
Supply fan VFD controlled to
maintain active duct static setpoint
Occ Cooling
Supply fan VFD controlled to
maintain active duct static setpoint
Occ Heating
Supply fan VFD controlled to
maintain active duct static setpoint
Unocc Standby
Supply fan is OFF
Unocc Cooling
Supply fan VFD controlled to
maintain active duct static setpoint
Unocc Heating
Supply fan VFD controlled to
maintain active duct static setpoint
Morning Warm-Up Supply fan VFD controlled to
maintain active duct static setpoint
Supply Fan Control
•
A Series 100 unit configured for VAV has a sup
-
ply fan VFD and a duct static pressure transducer
installed at the factory.
• The duct static pressure transducer sends a 0–5 VDC
signal to the IPU board according to the static pres-
sure it is sensing.
• The IPU board reads the 0–5 VDC input and then
sends a 0–10 VDC signal out to the VFD to control
the speed to the active duct static pressure setpoint.
Duct Static Reset
•
A Series 100 unit configured for VAV has the abil
-
ity to reset the active duct static pressure setpoint.
• Duct static reset can be initiated in one of two
ways:
• Hardwired: 0–5 VDC signal connected to
CTB1, terminals 25, 26, and 27
• BAS: A 0–5 command sent to the unit via
the BAS, BACnet MS/TP point AV05. Duct
pressure reset BAS must be User Enabled.
Duct pressure reset BAS can be found in the
SERVICE menu.