JOHNSON CONTROLS
31
SECTION 2 – INSTALLATION
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
2
FIGURE 7 -
FIELD CONTROL WIRING - INPUTS
LD08184D
WIRING NOTES
1. Wiring shown indicates typical wiring. Refer to IOM for more detailed wiring methods and options.
2. All wiring is Class 2, low voltage.
3. Maximum power available from the 24VAC terminal is 40VA.
4. Use shielded wire where shown.
5. Potentiometer application shown. As an alternative, signal inputs can be driven from an analog output of a third party controller. Note: Input
resistance is 15 K ohms.
6.
The FlexSys Underfloor Relative Humidity Sensor is field supplied. In addition to two wires that transmit the 0–5VDC signal from the sen
-
sor to the IPU board, the Underfloor Relative Humidity Sensor also needs to be powered. The type of voltage required to power the sensor
depends on the sensor selected. When the sensor uses 24VAC, additional wires must be run to terminal 1 (24VAC) and terminal 2 (24VAC
COM) of the CTB1 terminal block. When the sensor requires a different power source than 24VAC, it must be field supplied.
Supply Air Temp. Setpoint Reset
Duct Pressure Setpoint Reset
25
26
22
DSP- (DUCT STATIC RESET -)
DSP+ (DUCT STATIC RESET +)
+5V (DUCT STATIC SP + 5V)
+5V (SAT SP + 5V)
URH - (FLEXSYS UNDERFLOOR RH -)
URH + (FLEXSYS UNDERFLOOR RH +)
SHLD - (SHIELD (GND))
SHLD - (SHIELD (GND))
ZR - (ZONE TEMP SENSOR -)
ZR + (ZONE TEMP )
W2 - (2nd STAGE HEATING)
Y2 - (2nd STAGE COOLING)
Y1 - (1st STAGE COOLING)
G - (FAN (G))
SMK3 - (SMOKE PURGE 3)
SMK2 - (SMOKE PURGE 2)
SMK1 - (SMOKE PURGE 1)
OCC - (OCCUPIED/UNOCCUPIED)
SD - (SHUTDOWN)
24V - (24VAC)
24V -
(24VAC)
COM -
(24VAC
COM)
W1 - (1st STAGE HEATING)
SHLD - (FLEXSYS SLAB SENSOR -)
SHLD + (FLEXSYS SLAB )
SAT - (SUPPLY AIR TEMP RESET -)
SAT + (SUPPLY AIR TEMP RESET +)
1
Source Supply for
Remote Sensors of
Controls 40VA Max
CTB1 FIELD CONTROL WIRING (INPUTS)