SECTION 2 – INSTALLATION
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
2
TABLE 6 -
MISCELLANEOUS ELECTRICAL DATA
DESCRIPTION
NOMINAL VOLTAGE
208V
230V
460V
575V
380V
AMPS
AMPS
AMPS
AMPS
AMPS
Control Transformer 750 VA
3.6
3.3
1.6
1.3
2.0
Control Transformer 1.0 KVA
4.8
4.4
2.2
1.8
2.6
Convenience Outlet
9.6
8.7
4.4
3.5
NA
Gas Heat
9.6
8.7
4.4
3.5
5.3
TABLE 7 -
COMPRESSOR DATA (R-410A)
MODEL
COMPRESSOR
NOMINAL VOLTAGE
QUANTITY
MODEL
208/230V
460V
575V
RLA
LRA
RLA
LRA
RLA
LRA
070
6
ZP120
33.3
239
17.9
125
12.8
80
075
2
ZP154
51.3
300
23.1
150
19.9
109
4
ZP137
48.1
245
18.6
125
14.7
100
080
4
ZP154
51.3
300
23.1
150
19.9
109
2
ZP137
48.1
245
18.6
125
14.7
100
090
4
ZP182
55.8
340
26.9
173
23.7
132
2
ZP154
51.3
300
23.1
150
19.9
109
105
3
ZP182
—
—
26.9
173
23.7
132
3
ZP235
—
—
30.8
229
25.0
180
NOTE:
RLA data is per compressor.
TABLE 8 -
ELECTRIC HEAT AMP DRAW
kW*
NOMINAL VOLTAGE
208/3/60
230/3/60
460/3/60
575/3/60
AMPS
AMPS
AMPS
AMPS
80
193
193
96
80
108
260
260
130
109
150
—
—
181
151
200
—
—
241
201
250
—
—
301
251
*NOTE:
Heaters are sized as follows:
• 208V heaters are rated at 208V
• 230V heaters are rated at 240V
• 460V heaters are rated at 480V
• 575V heaters are rated at 600V
TABLE 9 -
AIRFLOW AND ENTERING AIR/AMBIENT LIMITATIONS
Limitations
Model Size
70
75
80
90
105
Minimum Airflow at Standard Design
Conditions. CFM* (min to max)
14,000–
32,000
14,000–
32,000
14,000–
32,000
18,000–
36,000
20,000–
36,000
Entering Wet Bulb Temp (°F) (min/max)
57/75
57/75
57/75
57/75
57/75
Entering Dry Bulb Temp (°F) (min/max)
68/90
68/90
68/90
68/90
68/90
Ambient Temp (°F) without Low Amb option
50/120
50/120
50/120
50/120
50/120
Ambient Temp (°F) with Low Amb option
0/120
0/120
0/120
0/120
0/120
*NOTE:
Cooling only units