JOHNSON CONTROLS
177
SECTION 8 – SERVICE
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
8
TABLE 66 -
FAULT AUTO - RESET
HISTORY
SCREEN
WORDING
DESCRIPTION
RESET
HOW WHEN UNIT
TYPE IS
STATUS
SCREEN
WORDING
FAULT
OUTPUT
TYPE
AUTO RESET-
COMPRESSOR
SYSTEM * CLEAR
See description below
Auto
Reset
AUTO RESET-
COMPRESS
SYSTEM * TRIP 1
The safety input chain is open (faulted)
for more than two seconds with either or
both compressor of the system on and
this is the first trip in a 120 minute span
Auto
Reset
Comp System
* Status Safety
Trip
Cooling
Heating
Fault
AUTO RESET
COMPRESSOR
SYSTEM * TRIP 2
The safety input chain is open (faulted)
for more than two seconds with either or
both compressor of the system on and
this is the second trip in a 120 minute
span
Auto
Reset
Comp System
* Status Safety
Trip
Cooling
Heating
Fault
AUTO RESET-
LOW SUCTION
TEMP
Either is compressor on and the
temperature - suction is less than
or equal to the suction low limit for
10 continuous seconds and after
the compressor was turned off the
temperature did not rise above the limit.
Auto
Reset
Comp System
* Status Safety
Fault
Sensor/
Misc Fault
AUTO RESET-
LPCO * TRIP 1
The low pressure cutout input chain
is open (faulted) for more than two
seconds with either or both compressor
of the system on and this is the first trip
in a 120 minute span
Auto
Reset
Comp System
* Status Safety
Trip
Cooling
Heating
Fault
AUTO RESET-
LPCO * TRIP 2
The low pressure cutout input chain
is open (faulted) for more than two
seconds with either or both compressor
of the system on and this is the second
trip in a 120 minute span
Auto
Reset
Comp System
* Status Safety
Trip
Cooling
Heating
Fault
AUTO RESET -
MSAT SENSOR
MS supply air temp current sensor is out
of range for >= 10 seconds.
Auto
Reset
Unit Type Is FlexSys
Sensor/Misc
Status Safety
Lockout
Sensor/
Misc Fault
AUTO RESET -
POWER FAIL
Power is lost when the unit operating
state is run
Auto
Reset
AUTO RESET -
RAT SENSOR
Return air temp current sensor is out of
range for >= 10 seconds
Auto
Reset
Sensor/Misc
Status Safety
Fault
Sensor/
Misc Fault
AUTO RESET
- REMOTE I/O
COMM
No communication from the i/o board for
>= 5 seconds
Auto
Reset
Sensor/
Misc Fault
AUTO RESET -
STAGED INPUT
The control has a cooling and heating
thermostat input at the same time for a
period greater than 10 seconds
Auto
Reset
Sensor/Misc
Status Safety
Lockout
Sensor/
Misc Fault
AUTO RESET
- ZONE TEMP
SENSOR
Zone temp current sensor is out of range
for >= 10 seconds
Auto
Reset
Unit Type Is VAV And
Night Set Back is User
Enabled Or Unit Type
Is Set To CV And The
Control Method Is
Set To Zone Sensor
Hardwired
Sensor/Misc
Status Safety
Lockout
Sensor/
Misc Fault
* Can Be 1, 2, Or 3