SECTION 6 - JLG CONTROL SYSTEM
3121714
6-83
99
19
GROUND SENSOR REF VOLTAGE OUT OF RANGE
The UGM has detected reference voltage is out of
range: 2.3V < Reference Voltage <
2.7V(debounced for 100ms)
Power cycle
99
20
PLATFORM SENSOR REF VOLTAGE OUT OF
RANGE
The UGM detects that its reference voltage being
reported by PM out of range (4.8V < voltage <
5.2V); debounced for 100ms
Power cycle
99
21
GROUND MODULE FAILURE - HIGH SIDE DRIVER
CUTOUT FAULTY
The UGM footswitch input J7-15 is LOW
Power cycle
99
22
PLATFORM MODULE FAILURE - HWFS CODE 1
The PM detects that its V(low) FET has failed and
reports this fault to the UGM
Power cycle
99
24
FUNCTIONS LOCKED OUT - MACHINE NOT CON-
FIGURED
The machine is powered up and no model has been
selected yet in the MACHINE SETUP menu
Power cycle
99
27
GROUND MODULE CONSTANT DATA UPDATE
REQUIRED
The UGM detects one of the following conditions
when software type is ‘P’ or ‘B’: The Version Verifi-
cation Word #1 or the Version Verification Word #2
values located in the constant data sector of flash
memory (found on constant data spreadsheet tab
pstConstantDataVersion) do not match the values
located in the code area of flash memory. The Ver-
sion Major value located in the constant data sector
of flash memory (found on constant data spread-
sheet tab pstConstantDataVersion) does not match
the value located in the code area of flash memory.
A different application code or constant data ver-
sion is programmed so that the values match;
Power cycled
99
44
CURRENT FEEDBACK GAINS OUT OF RANGE
One or more of the current feedback gains that are
calculated and written to flash memory during the
JDES manufacturing test process are detected as
being out of range
Power cycle
99
45
CURRENT FEEDBACK CALIBRATION CHECKSUM
INCORRECT
The current feedback gains checksum that is calcu-
lated and written to flash memory during the JDES
manufacturing test process is detected as being
incorrect
Power cycle
99
49
MACHINE CONFIGURATION OUT OF RANGE -
CHECK ALL SETTINGS
UGM has detected an anomaly in EEPROM with
regard to the Machine Setup configuration.
Power cycle
99
77
LSS CORRUPT EEPROM
MACHINE SETUP ->LOAD SYSTEM ≠ NO and one of
the following conditions:
UGM determines LSS-stored values for Unloaded
weight in Indirect 0x100≠ 0x108 or UGM deter-
mines LSS-stored values for Accessory weight in
Indirect memory≠ 0x10A; UGM determines LSS-
stored checksum1 in memory ≠ checksum 2 in
memory
Power cycle
99
79
FUNCTIONS LOCKED OUT - GROUND MODULE
SOFTWARE VERSION IMPROPER
Ground software has been installed on a UGM with
a ST10F274 processor (Hardware Rev < 6), which
does not have guaranteed flash storage in the sec-
tor where Constant Data is written.
Power cycle
99
86
GROUND MODULE VLOW FET FAILURE
VLow FET determined to be failed on Startup; UGM
unable to read high-sensing inputs.
Power cycle
99
167
PUMP COMMAND ERROR
Master Traction Module determines that an incon-
sistency has occurred between the Pump Enable
bits and the Pump commands; Pump enable bit =
set, but Pump Command = 0
Power cycle
Table 6-17. Diagnostic Trouble Codes
DTC Cat
DTC Num
DTC Text
Fault Description
Solution
Summary of Contents for E450A
Page 2: ......
Page 22: ...SECTION 1 SPECIFICATIONS 1 4 3121714 Figure 1 2 Maintenance Lubrication Diagram...
Page 51: ...SECTION 3 CHASSIS TURNTABLE 3121714 3 11 1001116232 A Figure 3 9 Drive Limit Switch...
Page 64: ...SECTION 3 CHASSIS TURNTABLE 3 24 3121714 1 0 Figure 3 18 Drive Hub Sheet 1 of 2...
Page 76: ...SECTION 3 CHASSIS TURNTABLE 3 36 3121714 Figure 3 27 Swing Components...
Page 96: ...SECTION 3 CHASSIS TURNTABLE 3 56 3121714 GENERATOR Figure 3 30 On Board Generator...
Page 116: ...SECTION 3 CHASSIS TURNTABLE 3 76 3121714 NOTES...
Page 343: ...SECTION 6 JLG CONTROL SYSTEM 3121714 6 27 CONNECTOR Figure 6 10 Power Module LH 1001192212 D...
Page 344: ...SECTION 6 JLG CONTROL SYSTEM 6 28 3121714 Figure 6 11 Power Module RH CONNECTOR 1001178339 E...
Page 479: ......