JEVEN UV-CONTROL G1

Installation Guide

Dokument Nr 500-00039 
Revision B

Summary of Contents for UV TURBO UV-CONTROL G1

Page 1: ...JEVEN UV CONTROL G1 Installation Guide Dokument Nr 500 00039 Revision B ...

Page 2: ...URES 3 TECHNICAL DATA 3 DELIVERY CHECK 4 ELECTRICAL INSTRUCTION 5 WIRING 6 SETTINGS AND OPERATIONS 7 21 MODBUS INSTALLATION 22 MODBUS COMMUNICATION 23 MODBUS CHANGE IP ADRESS 24 26 JEVEN UV Control Installation 2 Rätt till ändringar förbehålles ...

Page 3: ...operating time is reached and alarms When the maximum operating time is reached there is a possibility to reset the time if replace of an individual UV lamp before the maximum operating time has been reached should not the time be reset Sum alarm from from Jeven UV Control can be passed to an superior system by a potential free contact Start and stop of UV Turbo filter is selectable between Manual...

Page 4: ... bled and put into operation Contact Jeven AB for handling of defective material Delivery includes Jeven UV Control Safety switch Connected cables 5m or 10 m Jeven Plug Playbox 1 piece hood Mounted on the ceiling of the hood 4 Rätt till ändringar förbehålles JEVEN UV Control Installation Rätt till ändringar förbehålles ...

Page 5: ...ELECTRICAL INSTRUCTION 5 Rätt till ändringar förbehålles JEVEN UV Control Installation ...

Page 6: ...WIRING 6 Rätt till ändringar förbehålles JEVEN UV Control Installation ...

Page 7: ...op of the UV Turbo filters monitoring the UV lamps and keeping track of the UV lamps operating time As well as the ability to adjust the alarm limit for the ampere measurement if for example retrofitted into one or more UV Turbo 7 Rätt till ändringar förbehålles JEVEN UV Control Installation ...

Page 8: ...3 Start Stop by external signal 2 RUN TIME 2 1 Read current run time 3 ALARM 3 1 Alarm UV lamp 3 2 Alarm run time 3 3 Alarm cleaning 3 4 Sum alarm 3 5 Operation indication 4 PROGRAMMING ALARM LIMIT CONTENT Rätt till ändringar förbehålles JEVEN UV Control Installation 8 Rätt till ändringar förbehålles ...

Page 9: ...SETTINGS AND OPERATIONS 1 CONTROL FUNKTION 1 1 Manual start stop To stop the UV purification manual press Esc 9 Rätt till ändringar förbehålles JEVEN UV Control Installation ...

Page 10: ...2 Set parameter and 3 WEEKLY TIMER Here you can use up to 3 different time programs D1 D2 and D3 Example D1 D2 M T W T F S S On1 On2 07 00 10 00 Off1 Off2 16 00 14 00 Exit the program menu by pressing Esc until time and date appear on screen then press arrow 10 Rätt till ändringar förbehålles Rätt till ändringar förbehålles JEVEN UV Control Installation ...

Page 11: ...ate Start Stop by 24VDC signal Start of the system occurs when input I8 on Siemens LOGO will go in high state over 79VAC Stop of system occurs when the voltage level is below 30VAC the input I8 on Siemens LOGO will go in low state Internal 230 VAC External 230VAC Relay 24VDC External 24VDC External 24VDC Relay diagram JEVEN UV Control Installation 11 Rätt till ändringar förbehålles ...

Page 12: ...Current operating time is read by simultaneously pressing Esc UV lamps have a lifespan of 8 000 h then they should be replaced The system will indicate when the run time of 8 000 h has been reached JEVEN UV Control Installation 12 Rätt till ändringar förbehålles ...

Page 13: ... is determined which UV light is broken byts den The alarm is reset automatically when the current limit returns to the normal level 3 2 Alarm run time Jeven UV Control has built in control of the run time of the UV lamp the system will give an alarm when 8 000 h are reached which is the lifespan of the UV lamps Replace all UV lamps and reset run time by pressing ESC JEVEN UV Control Installation ...

Page 14: ...sibility to set a cleaning interval in the Siemens LOGO The service function is OFF by default Set the cleaning status to ON Adjust the cleaning interval if necessary Default time is set to 10h On 00010 JEVEN UV Control Installation 14 Rätt till ändringar förbehålles ...

Page 15: ...0VAC VDC to the potential free relay output Q1 NO on Siemens LOGO Alarm External Max 240VAC VDC 3 4 Operation indication It is possible to get an operation indication from Simens LOGO Connect any voltage Max 240VAC VDC to the potential free relay output Q4 NO on the Siemens LOGO Operation indication External Max 240VAC VDC JEVEN UV Control Installation 15 Rätt till ändringar förbehålles ...

Page 16: ...er for a more stable current measurement This means that the visual value shown on the Finder 71 51 display is only a fictional value Jeven UV Control is delivered pre programmed and calibrated for each project kitchen The following is instructions for calibration of the system Start the system and check all filters that the LED labeld UV lights blue then read on the Finder 71 51 display what the ...

Page 17: ...ly functional 40A one 1 UV lamp off 34A The alarm limit should then have a value of 37A To check the current alarm limit and the ability to adjust it you need to enter the Finder 71 51 programming view Accessing the programming view is achieved by holding down the Set Reset and Select buttons at the same time for 3 seconds JEVEN UV Control Installation 17 Rätt till ändringar förbehålles ...

Page 18: ...o proceed Window 2 Here is the value of the internal power transformer this must not be changed Press the SET RESET button to proceed Window 3 Here you choose if you want to measure under or overcurrent the system should me asure undercurrent and may not change Press the SET RESET button to proceed JEVEN UV Control Installation 18 Rätt till ändringar förbehålles ...

Page 19: ...er is on the window As in exemlett above we would have 37A Press the SET RESET button to proceed Window 5 Here is the value of the preprogrammed hysteresis value this must not be changed Press the SET RESET button to proceed Window 6 T1 Here you program a delay of outgoing alarm when it has detected a current loss Finder 71 51 is programmed with a delay of 10 seconds This value should not be chang...

Page 20: ...ment the delay is programmed with 10 seconds for the current to be stable before mea surement This value should not be changed Press the SET RESET button to proceed Window 8 Selection of memory function memory function should not be used Do not change Press the SET RESET button to proceed JEVEN UV Control Installation 20 Rätt till ändringar förbehålles ...

Page 21: ... view If there is a need to continue from the beginning again press the SELECT button Start the system again and take down a grease collector the system will now detect the power loss and generate an alarm Refit the grease collector and reset the alarm by pressing ESC JEVEN UV Control Installation 21 Rätt till ändringar förbehålles ...

Page 22: ...ple below Connect one side of the Ethernet cable to Siemens LOGO X1 P1 IE LAN see picture below LOGO 8 FS4 192 168 0 3 Modbus Master 192 168 0 50 Local PC MODBUS TCP Connect the other side of Ethernet cable to the superior system see example below JEVEN UV Control Installation 22 Rätt till ändringar förbehålles ...

Page 23: ...rs commu nicates with one and the same Logo Default is LOGO configured in slave mode The maximum update time for Modbus communication is 100 ms Function LOGO Modbus Start Stop V0 0 1 Coil Service alarm V1 0 9 Coil Sum alarm V1 1 10 Coil Operation indication V1 2 11 Coil Default IP Adress 192 168 0 3 Netmask 255 255 255 0 Netmask 255 255 255 0 JEVEN UV Control Installation 23 Rätt till ändringar fö...

Page 24: ...ry to change the IP address to match the IP address of the facility Follow the steps below to set the correct IP address Press the down arrow Then press ESC Set the cursor to Stop and press OK JEVEN UV Control Installation 24 Rätt till ändringar förbehålles ...

Page 25: ...MODBUS CHANGE OF IP ADRESS IN SIEMENS LOGO Stop program Yes and press OK Set the cursor to Network and press OK IP Address press OK JEVEN UV Control Installation 25 Rätt till ändringar förbehålles ...

Page 26: ...umbers and move si deways When the correct IP address is set press OK Do the same to change the Subnet Mask When both addresses are set press ESC twice Set the cursor to Start and press OK Start program Yes and press OK The IP address has now been changed JEVEN UV Control Installation 26 Rätt till ändringar förbehålles ...

Page 27: ...CONTACT Jeven AB 46 0 270 731 40 Växelgatan 15 jeven jeven se S 826 40 Söderhamn www jeven se 27 Rätt till ändringar förbehålles Rätt till ändringar förbehålles JEVEN UV Control Installation ...

Page 28: ...jeven se Välkommen att kontakta oss för mer information jeven jeven se 46 270 73140 ...