Jetter AG
Parameterization | 8
User Manual – JXM-IO-E30
57 / 70
Emergency Error Codes
Code
Description
0x0000
No error or error reset
0x1000
Generic error
0x2300
Total current is too high
0x3100
Voltage exceeding the required tolerance range
0x4200
Device temperature is too high
0x8110
CAN data overrun (lost objects)
0x8130
Life guard error or heartbeat error
0x8140
Recovered from
Bus-Off
state
0x8210
Processing errors due to incorrect length of PDOs
0x8220
PDO length exceeded
0xff00
Configuration error on the device
0xff01
I/O-Port OVERVOLTAGE
0xff02
I/O-Port OVERCURRENT
0xff03
I/O-Port SUPPLYFAULT
0xff05
I/O-Port OPEN_CIRCUIT
0xff06
I/O-Port TIMEOUT
0xff07
I/O-Port CC_UNLOCK
Tab. 57:
Emergency Error Codes