10.4 Shielded Data and I/O Lines
Operating Parameters (EMC) - Immunity to Interference
Parameters Value(s)
Standard
Asymmetric RF,
amplitude-modulated
Frequency band 0.15 - 80 MHz
Test voltage 3 V
AM 80 % with 1 kHz
Source impedance 150 Ohm
Criterion A
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-6
Burst
(Bursts)
Test voltage 1 kV
tr/tn 5/50 ns
Repetition rate 5 kHz
Criterion A
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-4
Voltage Surges,
asymmetric
(line to earth)
tr/th 1.2/50 µs
Common mode launching 1 kV
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-5
Operating Parameters EMC - Immunity to Interference
Functional Ground Connection
Parameters Value(s)
Standard
RF, asymmetric
Frequency band 0.15 - 80 MHz
Test voltage 3 V
AM 80 % with 1 kHz
Source impedance 150 Ohm
Criterion A
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-6
Bursts
Test voltage 1 kV
tr/tn 5/50 ns
Repetition rate 5 kHz
Criterion A
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-4