JX3-BN-CAN
Appendix
Note!
At mounting the JX3 modules, a minimum clearance above and below must be
maintained. The minimum clearance above is 30 mm, the minimum clearance
below is 25 mm.
The clearance is needed for dismounting the JX3 module from the JX3 backplane
module.
The first JX3 module requires a space of 31 mm width. Each further JX3 module
increases the width of a JX3 station by 25 mm.
The JX3 modules must be mounted in vertical position. Only at vertical mounting,
optimum heat dissipation of the modules is guaranteed.
Design
Dimensions (H x W x D in mm)
131 x 31 x 100
Weight
approx. 160 g
LED-sheeting
RAL 7035, light grey
JX3 module enclosure
Plastic RAL 7035, light grey
JX3 backplane module
Plastic RAL 5002, ultramarine blue
Installation
on DIN rail
EN 50022 - 35 x 7.5 or
EN 50022 - 35 x 15
Diagnostic indicators (LEDs)
4
Mounting position
Vertical
9.2 Connections
Module JX3-BN-CAN has been equipped with the following connections:
X10
Voltage supply for module JX3-BN-CAN and connected JX3 modules
2-pin female connector, contact spacing 3.5 mm, spring cage
X18
IN-interface for Jetter system bus
9-pin male SUB-D connector
X19
OUT-interface for Jetter system bus
9-pin female SUB-D connector
Jetter AG