JX2-IO16
10.5 Register Description
Jetter AG
81
These register array elements are for specifying the pulse stretching duration for
automatic pulse stretching.
If the value is 0 ms, automatic pulse stretching is disabled. When entering the
value 0, an active pulse stretching process will be completed. Then, automatic
pulse stretching will be disabled.
It is not allowed to enter a value for an input, as long as manual pulse
stretching for this input is active.
Register 3xx8 = 31 ... 38
Register 3xx9: Automatic pulse stretching -
Pulse stretching duration -
Input 1 ... 8
Function
Description
Read
Present pulse stretching duration
Write
New pulse stretching duration (will become
effective only on completion of the active pulse
stretching process).
Value range
0 ... 255 ms
Value after reset
0 ms (disabled)