6 Installation Guide
JetWeb
52
Jetter AG
System Bus Cable Specification
The following minimum requirements apply to the manufacture of the system bus
cable:
System Bus Cable - Technical Data
Function
Description
Core cross-sectional
area
1 MBaud:
0.25 - 0.34 mm
2
500 kBaud:
0.34 - 0.50 mm
2
250 kBaud:
0.34 - 0.60 mm
2
125 kBaud:
0.50 - 0.60 mm
2
Cable capacitance
maximum 60 pF/m
Resistivity
1 MBaud:
maximum 70
/km
500 kBaud:
maximum 60
/km
250 kBaud:
maximum 60
/km
125 kBaud:
maximum 60
/km
Number of cores
5
Shield
Complete shielding, no paired shielding
Twisting
Core pair CL and CH twisted.
Ω
Ω
Ω
Ω
Allowed cable lengths
Baud Rate
Max. cable
length
Max. tap line
length
Max. overall tap
line length
1 MBaud
30 m
0.3 m
3 m
500 kBaud
100 m
1 m
39 m
250 kBaud
200 m
3 m
78 m
125 kBaud
200 m
-
-
Note!
• The maximum cable length depends on the baud rate used and the number of
modules connected to the bus.
• When calculating the maximum line length, please take into account that each
module connected to the bus reduces the cable length by approx. 1 m.
Summary of Contents for JX2-IO16
Page 10: ...Table of Contents JetWeb 10 Jetter AG...
Page 18: ...1 Safety Instructions JetWeb 18 Jetter AG...
Page 22: ...2 Introduction JetWeb 22 Jetter AG...
Page 23: ...JX2 IO16 Jetter AG 23 3 Mounting Dimensions Fig 3 Front View JX2 IO16 Fig 4 Side View JX2 IO16...
Page 24: ...3 Mounting Dimensions JetWeb 24 Jetter AG Fig 5 Top View JX2 IO16...
Page 56: ...6 Installation Guide JetWeb 56 Jetter AG...
Page 68: ...9 Fast inputs Software filter JetWeb 68 Jetter AG...
Page 82: ...10 Pulse stretching JetWeb 82 Jetter AG...
Page 105: ...JX2 IO16 Appendix Jetter AG 105 Appendices...
Page 106: ...Appendices JetWeb 106 Jetter AG...
Page 123: ...JX2 IO16 Appendix Jetter AG 123...