NOTICE
DAMAGE TO THE DEVICE DUE TO IMPROPER
OPERATION
THIS HAZARD COULD DAMAGE THE DEVICE IF NOT AVOIDED
If the duration of the test pulses is in the range from
0.75 ms … 2 ms, they will result in undesired shutdowns at unpre-
dictable times. This statement applies irrespective of whether the
monitoring of external test pulses is switched on or off.
3.1 Electrical isolation concept
y
The digital inputs SDI00/SDI01/GND are isolated in relation to
SDI02/SDI03/GND
y
All inputs are isolated in relation to the 24 V supply.
y
All inputs are isolated in relation to the PE.
y
Maximum permissible isolation voltage: SELV/PELV
y
Maximum permissible input voltage: - 60 V ... 60 V
The servo amplifier provides a separate input for the STO request, a
feature for disabling the restart inhibit, and a separate relay contact for the
feedback.
3.2 Overview of DIL switch block S-ADR
Switch
Function
Slider position
For details
see chapter
10
Selector
switch
SBC
9
8
7
Test pulse
monitoring
STO
6
52
Jetter AG
Overview of the connections
JetMove 3000
Summary of Contents for JM-35 S1 Series
Page 2: ...2 Jetter AG JetMove 3000...
Page 4: ...4 Jetter AG JetMove 3000...
Page 6: ...6 Jetter AG JetMove 3000...
Page 8: ...8 Jetter AG JetMove 3000...
Page 40: ...40 Jetter AG JetMove 3000...
Page 68: ...68 Jetter AG Validation JetMove 3000...
Page 103: ...JM 3000 DIL S ADR STO STO STO SBC Jetter AG 103 DE CN IT EN JetMove 3000...
Page 106: ...SBC A2 106 Jetter AG JetMove 3000...
Page 119: ...JSC 110 1 RS STO JSC 110 1 RS 10 JSC 110 1 RS STO Jetter AG 119 DE CN IT EN JetMove 3000...
Page 120: ...5 5 1 STO STO y y y y y y 7 STO 1 STO 2 STO 7 STO 120 Jetter AG JetMove 3000...
Page 122: ...5 3 STO y y y y y y 10 1 24 V DC 2 4 S ADR SBC 10 STO 122 Jetter AG JetMove 3000...