5.2 Motor Protection
Jetter AG
41
5.2.3
Motor Overload Protection to UL
The UL standard prescribes a motor overload detection for a servo amplifier that
meets the following points:
The "trip current" is defined to be 1.15 times the user-set continuous rated current.
• If the average motor current corresponds to the trip current, the overload
protection has to switch off the motor after a limited time
• If the average motor current is 2 times higher than the trip current the overload
protection has to switch off the motor after at least 8 minutes.
• If the average motor current is 6 times higher than the trip current, the overload
protection has to switch off the motor after at least 20 seconds.
This protection (error message 31 will occur) can be parameterized only through the
nominal current value.
The motor overload protection is always active and cannot be deactivated.
Important
Because of the fact that after reset the motor overload calculation always starts
with zero, the result is wrong if the motor is already hot when the digital servo
amplifier JetMove 208-480 is switched on (i. e. at the time of connecting the 24 V
logic power supply).
Summary of Contents for JM-208-480-OEM
Page 1: ...User Manual JM 208 480 Digital Servo Amplifier 60870619 We automate your success...
Page 22: ...1 Safety Instructions 22 Jetter AG...
Page 34: ...4 Physical Dimensions 34 Jetter AG...
Page 42: ...5 Technical Data 42 Jetter AG...
Page 82: ...9 Diagnostics 82 Jetter AG...
Page 86: ...10 Connection Diagrams 86 Jetter AG...
Page 106: ...13 Safe Standstill Option 106 Jetter AG...
Page 116: ...15 Ordering Information 116 Jetter AG...
Page 117: ...JetMove 208 480 Appendices Jetter AG 117 Appendices...
Page 118: ...Appendices 118 Jetter AG...