Status Monitoring
The amplifier LEDs indicate the operating status of the digital servo amplifier.
LEDs at JetMove D203
LED
Color
Status
Description
VCC1
Green
is lit
Logic module voltage is OK
L1
Yellow
is lit
Axis is standing still (speed = 0)
L2
Yellow
is lit
A voltage of 24 V is applied to the input of
the positive limit switch (LIMIT+).
L3
Yellow
is lit
A voltage of 24 V is applied to the input of
the negative limit switch (LIMIT-).
VCC1
L 3
L 2
L 1
Notice!
The 7-segment display of the output stage indicates the operating and fault
conditions of the digital servo amplifier JetMove D203. The various display
modes are set by the Motion Setup. Mode 0 (default) is used for normal operation
and mode 1 for commissioning.
JetMove D203 - Seven-Segment Display
Mode 0: Normal Operation
Display
Status
Description
0
NOT READY TO BE
SWITCHED ON
Initialization of amplifier functions
1
SWITCH-ON INHIBIT
Initialization completed. Safe state. Is
achieved after initialising and after
acknowledging errors.
The drive controller can be switched
on.
2
READY TO BE SWITCHED
ON
Drive controller has been disabled by
software command.
The drive controller can be switched
on.
3
SWITCHED ON
DC link monitoring is activated.
4
OPERATION_ENABLED
The drive controller has been
enabled.
Summary of Contents for JetMove D203
Page 1: ...User Manual JM D203 230 Digital Servoamplifier 60870727 We automate your success...
Page 10: ...Table of Contents 10 Jetter AG...
Page 36: ...4 Physical Dimensions 36 Jetter AG...
Page 46: ...5 Technical Data 46 Jetter AG...
Page 92: ...11 Option S1 STO 92 Jetter AG...
Page 133: ...JetMove D203 Appendix Jetter AG 133 Appendices...
Page 134: ...Appendices 134 Jetter AG...