Jetter AG
Technical specifications | 4
User Manual – JetControl 365MC
23 / 148
4.6.3 DC power supply inputs and outputs
Immunity to
interference
Parameter
Values
Standards
Asymmetric RF, amplitude-modulated
Frequency band
0.15 MHz … 80 MHz
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-6
Test voltage
10 V
AM 80% at 1 kHz
Source impedance
150 Ω
Criterion A
Bursts
Test voltage
2 kV
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-4
tr/tn 5/50 ns
Repetition frequency
5 kHz
Criterion A
Surge voltages, symmetric, line to cable
Series-mode interference tr/th 1.2/50 µs
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-5
0.5 kV
Surge voltages, asymmetric, line to earth
Common-mode interfer-
ence
tr/th 1.2/50 µs
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-5
1 kV
Tab. 17:
DC power supply inputs and outputs