
Jetson
www.JetsonHVAC.com
62
Total Supply Voltage
WARNING
Live Electrical Components!
Failure to follow all electrical safety
precautions when exposed to live electrical
components could result in death or serious
injury. When necessary to work with live
electrical components, have a qualified
licensed electrician or other individual who
has been properly trained in handling live
electrical components perform these tasks.
Measure each leg of the supply voltage at the line
voltage disconnect switches. For units with a
nameplate voltage of 208/230 volt, the readings
must fall within the range of 180253 volts. For
units with a nameplate voltage of 460 volts, the
readings must fall within the range of 414-506
volts. If voltage on any leg does not fall within
tolerance, notify the power company and request
correction of this situation before connecting to or
operating the unit. Inadequate voltage to the unit
will shorten the life of relay contacts and
compressor motors.
Voltage Imbalance Between Phases
Excessive voltage imbalance between phases in a
three- phase system will cause motors to overheat
and eventually fail. Maximum allowable
imbalance is 2 percent. Voltage imbalance is
defined as 100 times the maximum deviation of
the three voltages (three phases) subtracted from
the average (without regard to sign), divided by
the average voltage.
EXAMPLE:
If the three voltages measured at the line voltage
fused disconnect are 221 volts, 230 volts and 227
volts, the average would be:
221 + 230 + 227
3
= 226 𝑣𝑜𝑙𝑡𝑠
The percentage of imbalance is then:
100 (226 − 221)
226
= 2.2%
In the preceding example, 221 is used because it
is the farthest from the average. The 2.2 percent
imbalance that exists exceeds maximum
allowable imbalance by 0.2 percent. This much
imbalance between phases can equal as much as
20 percent current imbalance with a resulting
increase in winding temperature that will decrease
compressor motor life.
Equipment Grounding
CAUTION
Use Copper Conductors Only!
Failure to use copper conductors could result in
equipment damage as unit terminals are not
designed to accept other types of conductors.
Provide proper grounding at the connection point
provided in the unit control panel.
Unit Power Wiring
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing
could result in death or serious injury.
Disconnect all electric power, including
remote disconnects before servicing. Follow
proper lockout/tagout procedures to ensure
the
power
cannot
be
inadvertently
energized.
The installing contractor must connect appropriate
power wiring (with fused disconnects) to the unit-
mounted, non-fused disconnect in the power
section of the unit control panel. Electrical
schematics and component location drawings are
also mounted on the inside of the control panel
door.
Summary of Contents for FWCD Series
Page 1: ...FWCD Series Chillers Installation Operation Maintenance...
Page 2: ...Jetson www JetsonHVAC com 2...
Page 30: ...Jetson www JetsonHVAC com 30 Figure 4 FWCD array dimensions brazed plate condenser...
Page 31: ...Jetson www JetsonHVAC com 31 Figure 5 FWCD dimensions shell and tube condenser...
Page 32: ...Jetson www JetsonHVAC com 32 Figure 6 FWCD array dimensions shell and tube condenser...
Page 33: ...Jetson www JetsonHVAC com 33 Figure 7 FWCD dimensions remote condenser...
Page 34: ...Jetson www JetsonHVAC com 34 Figure 8 FWCD array dimensions remote condenser...
Page 82: ...Jetson www JetsonHVAC com 82 Wiring Figure 26 FWCD wiring schematic...
Page 83: ...Jetson www JetsonHVAC com 83 Figure 27 FWCD wiring schematic continued...
Page 84: ...Jetson www JetsonHVAC com 84 Figure 28 FWCD dual circuit secondary wiring schematic...
Page 85: ...Jetson www JetsonHVAC com 85 Figure 29 FWCD dual circuit secondary wiring schematic continued...
Page 86: ...Jetson www JetsonHVAC com 86 Figure 30 Field wiring FWCD single unit single circuit...
Page 87: ...Jetson www JetsonHVAC com 87 Figure 31 Field wiring FWCD single unit dual circuit...