Jazz JZ20-J-R16HS User Manual Download Page 1

 

Unitronics 

 

 

Jazz

®

 

User Guide 

JZ20-R10/JZ20-J-R10 
JZ20-R16/JZ20-J-R16 

 

JZ20-J-R16HS 

 

 

6 Digital Inputs including 2 HSC, 4 Relay Outputs 

 

6 Digital Inputs including 2 HSC, 2 Analog/Digital Inputs,  

2 Analog Inputs, 6 Relay Outputs 

 

 

6 Digital Inputs including 3 HSC/Shaft-encoder,  
2 Analog/Digital Inputs, 2 Analog Inputs, 6 Relay Outputs

 

 

 

General Description 

 

The products listed above are micro-PLC+HMIs, rugged programmable logic controllers that comprise 
built-in operating panels. 

Detailed Installation Guides containing the I/O wiring diagrams for these models, technical specifications, 
and additional documentation are located in the Technical Library in the Unitronics website:   

https://unitronicsplc.com/support-technical-library/

 

  

Alert Symbols and General Restrictions 

When any of the following symbols appear, read the associated information carefully. 

Symbol 

Meaning 

Description 

 

Danger 

The identified danger causes physical and property damage. 

 

Warning 

The identified danger could cause physical and property damage. 

Caution

 

Caution 

Use caution. 

 Before using this product, the user must read and understand this document.  

 All examples and diagrams are intended to aid understanding, and do not guarantee operation. 

Unitronics accepts no responsibility for actual use of this product based on these examples. 

 Please dispose of this product according to local and national standards and regulations. 

 Only qualified service personnel should open this device or carry out repairs. 

 

 Failure to comply with appropriate safety guidelines can cause severe injury or property 

damage. 

 

 Do not attempt to use this device with parameters that exceed permissible levels. 

 To avoid damaging the system, do not connect/disconnect the device when power is on. 

 

Environmental Considerations 

 

 

 Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,  

moisture or rain, excessive heat, regular impact shocks or excessive vibration, in  
accordance with the standards given in the product’s technical specification sheet. 

 Do not place in water or let water leak onto the unit. 

 Do not allow debris to fall inside the unit during installation. 

 

 

Ventilation: 10mm space required between controller’s top/bottom edges & enclosure walls. 

 Install at maximum distance from high-voltage cables and power equipment. 

 

 

 

 

 

 

Summary of Contents for JZ20-J-R16HS

Page 1: ...e using this product the user must read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for...

Page 2: ...r for communication and cloning Integral USB Port This may be used for programming purposes Note the USB port and an Add on module cannot be physically connected at the same time Add on during install...

Page 3: ...s offering a terminal block with pitch of 5mm 26 12 AWG wire 0 13 mm2 3 31 mm2 Controllers offering a terminal block with pitch of 3 81mm 26 16 AWG wire 0 13 mm2 1 31 mm2 1 Strip the wire to a length...

Page 4: ...known to be non hazardous Please note that it is recommended to back up all data retained in RAM in order to avoid losing data when changing the battery while the power is switched off Date and time i...

Page 5: ...as part of a shaft encoder or as normal digital inputs If I0 I1 I4 are set as high speed counters without reset I2 I3 I5 can function as normal digital inputs 4 The following information concerns JZ20...

Page 6: ...as npn or as pnp In either case the n p pins must be connected Input wiring I0 I5 npn sink Input wiring I0 I5 pnp source Input wiring I6 I7 npn sink Input wiring I6 I7 pnp source JZ20 J R16HS Note The...

Page 7: ...tronics 7 HSC input wiring npn sink HSC input wiring pnp source Shaft encoder wiring npn sink Shaft encoder wiring pnp source Digital Outputs JZ20 R10 JZ20 J R10 JZ20 R16 JZ20 J R16 JZ20 J R16HS Outpu...

Page 8: ...in parallel with each inductive AC load JZ20 R10 JZ20 J R10 JZ20 R16 JZ20 J R16 JZ20 J R16HS Analog inputs Note Shields should be connected at the signal source Analog Input wiring current JZ20 R16 J...

Page 9: ...source or npn sink Galvanic isolation None Nominal input voltage 24VDC Input voltage pnp source 0 5VDC for Logic 0 17 28 8VDC for Logic 1 npn sink 17 28 8VDC for Logic 0 0 5VDC for Logic 1 I0 I5 I6 I7...

Page 10: ...d voltage 250VAC 24VDC Minimum load 1mA 5VDC Life expectancy 50k operations at maximum load Response time 10mS typical Contact protection External precautions required see Increasing Contact Life Span...

Page 11: ...messages Supports Remote Access MODBUS Supports MODBUS protocol Master Slave Baud rate According to add on port module USB Port type Mini B Galvanic isolation No Specification USB 2 0 compliant full s...

Page 12: ...aterials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warra...

Reviews: