Module 96-PA-RCM / 96-PA-RCM-EL
www.janitza.de
46
9.5 Module-relevant configuration with the
GridVis
®
software
The explanations of the measuring modes and the
settings can be found in section „9. Module-rele-
vant configuration“ on page 42.
·Select the device in the GridVis
®
software and
click on
Configuration
.
·Click on the symbolized connections to display
the corresponding settings.
·Mark the multifunctional channel L5 (terminals
29/30) or L6 (31/32) and select the measuring
mode:
-
Mode AC
or
-
RCM 0..20 / 4..20 mA
or
-
DC Power 0..20 / 4..20 mA
·Be sure to select the same measuring mode for
L6 as for L5.
INFORMATION
For notes on setting the limit value calculation, see section
Residual current limit values“ on page 29.
Fig. Measuring mode
Mode AC
Measuring modes
Mode AC
or
RCM 0..20 / 4..20 mA
In the measuring modes
Mode AC
and
RCM
, the
Residual Current
menu shows the settings for
both channels L5 and L6.