14.4 Configuration
14.4.1 General Settings
1
Demand Interval
: Kilowatt demand is a measure of the average rate at which kilowatt-hours are used
during a certain time interval. This can be a value range from 0-3600 seconds.
It does not affect any parameter other than demand kWh.
2
Demand Sub Intervals
: The demand interval can be broken down into subintervals. The meter calcula-
tes the average load in each subinterval as well as each Demand Interval.
3
Point Map
: The monitor is capable of supporting different register maps. The standard register map is
the UMG 804 Point Map that provides access to all of the features the module offers.
4
System Voltage
: Provide the nominal system voltage (line to line) for the source. If a line to neutral
single-phase source is being used input the line to neutral voltage. This is used in the calculation of the
CBEMA / ITIC voltage event calculations.
5
PT Ratio Scale
: provides a scaling factor for the voltage reference when using potential transformers
to scale voltage for medium voltage applications.
6
Smart Port Configuration
:
refer to sections „Panel Maps Configuration“.
Selecting the
Schneider Point Map
provides a different register map that
emulates the Schneider/Veris MCM/
BCM monitor in the event legacy
Schneider equipment is also being
used on a common system.
2
6
5
4
Important
: Always remember to select the
Update Settings
button to save settings.
INFORMATION
1
3
Summary of Contents for 14.02.001
Page 7: ...www janitza com UMG 804 7...
Page 30: ...UMG 804 www janitza com 30 8 3 Panel Maps Configuration 8 3 1 Top Feed...
Page 31: ...www janitza com UMG 804 31 PANEL 1 PANEL 2...
Page 32: ...UMG 804 www janitza com 32 8 3 2 Bottom Feed...
Page 33: ...www janitza com UMG 804 33 PANEL 1 PANEL 2...
Page 34: ...UMG 804 www janitza com 34 8 3 3 Single Row Sequential...
Page 35: ...www janitza com UMG 804 35 PANEL 1 PANEL 2...
Page 36: ...UMG 804 www janitza com 36 8 3 4 Single Row Odd Even...
Page 37: ...www janitza com UMG 804 37 PANEL 1 PANEL 2...
Page 42: ...UMG 804 www janitza com 42...
Page 63: ...www janitza com UMG 804 63 14 3 6 Busway Data Currently not available...