background image

Jaga Room Thermostat JRT-200 installation, setup & user manual

Features

•  for 2- and 4-pipe fan coil systems
•  heating and cooling mode (4-pipe)
•  heating and cooling mode (2-pipe)
•  automatic or manual fan speed control 
•  surface-mounting
•  2 programmable time zones 
•  0-10V output
•  valves 24V AC/DC or 230VAC
•  it is possible (at manual control) to allow the fan to run once “set point” is 

reached

Technical Data

Power Supply

24V AC/DC

Power Consumption

200 mA

Set Point Range

+10 > +40°C

Ambient

0 > +40°C

Relative Humidity

85% max

Backlight

Blue

Sensor 

NTC 10K

Accuracy

+ 1°C (step control by +0.5°C)

Protection Class

IP30

Housing

ABS to UL94-5 fire retardant plastic

Product-documentation: 

•  this manual is an integral part of the unit and must be handed over to the user 

after the installation of the device is completed in order to comply with applicable 

legal requirements.

•  please read the manual carefully so that you understand the information in order 

to ensure safety during installation, use and maintenance.

•  no liability is accepted for damage resulting from non-compliance with the 

guidelines in this installation manual.

Dimensions

M

M

4.25

6.5

3

2.8

9.3

14

9.7

13.4

1.2

1.4

0.4

CE-mark

The CE-mark symbolizes the compliance of the device with the following guide-

lines:

•  EN 61000-6-3:2007+A1:2011

•  EN 61000-3-2:2006+A1:2009+A2:2009

•  EN 61000-3-3:2008

•  EN 61000-6-1:2007

IMPORTANT: This manual will guide you through the installation, setup and use of the Jaga Room Thermostat JRT-200. Keep this manual in 

a safe place for future reference.

JRT-200

ATTENTION !!

1.5 m

The room thermostat must be installed at approx.

1.5 m above floor and out of reach of external influ-

ences such as direct sunlight, draught or other heat 

sources as they may impede the correct functioning 

of the thermostat. Nearby electric fires, televisions, 

wall or table lamps may prevent the thermostat from 

working properly.

Ensure that there will be enough space to allow easy 

access to the two retaining screws, located at the bot-

tom of the wall plate.

6

2.8

Mount  the JRT-200 Room thermostat on a wall re-
cessed box (60.3 mm fixing centers) or direct onto a flat 

wall using wall plugs. 

Deze handleiding in het NEDERLANDS:

Ce manuel en FRANÇAIS:

Dieses Handbuch auf DEUTSCH:

This manual in ENGLISH:

www.jaga.be/downloads/Briza/Manual_JRT200.pdf

Reviews: