5.5.4.3 View serial numbers and firmware versions
From this menu, operators will be able to access product serial numbers (PSNs) and system software
versions.
5.5.4.4 Loop state signal report
Loop state signal can be displayed in two formats: Table or plot. In both formats, the data related to the state
of every device on the selected loop is listed.
By pressing F2 or F3, the user can change the cycle on demand. Pressing F4 you can select Table or Graph.
5.5.4.5 Field device raw data report
Under this menu, users will have all the 10 bytes data from the field devices of the panel. This menu can be
used for diagnostic purpose. There are two formats available to view the data for users to choose from, one
is decimal format and the other is hexadecimal format.
By pressing F2 or F3, the user can change the address of the device to consult. Pressing F4 you can select
Decimal or Hexadecimal format.
5.5.4.6 Field device state signal value
From this sub-
menu, operators can review the “BkValue (mA)” which represents the background current
(refers to the loop current under “low voltage” period, when no device provides the answer current) and
“CurValue (mA)” which stands for the answer current from the designated device(s). The answer current is
how the device provide the (status normal, trouble, alarm).
By pressing F2 or F3, the user can change the address of the device to consult.
5.5.4.7 View advanced programming
After entering the advanced programming menu, user can view the actions/logic that are currently
programmed in the panel. Each action can be viewed by pressing F2 or F3 to index the action. See section
Error! Reference source not found.
for a description of the advanced programming syntax.
5.5.4.8 View addresses linked to a zone
Press 5 to enter the sub-menu to view addresses of loop devices assigned under designated zone(s). Users
can either enter the number of the zone by pressing the numeric keypad or press F2 or F3 to change the
zone. To exit the current window press F6.
Once the correct zone the user desires to access has been entered, the list of devices assigned to this zone
is displayed by the format of: Loop number-Device address (range).
5.5.4.9 View addresses used in a loop
In this submenu, users will be able to view the addresses used by a specific link. After accessing the menu
option, the user must select the link for which they wish to display the addresses used that will be displayed
on the screen ordered by type of equipment.