M-P2L1-1 EN
Page 25
Release Date: November 15, 2019
Rev 01
5.3.2.3 View disablements
Use this menu to obtain a description of the active disablements.
Press F1 to return to the first page, press F2 to view previous page, press F3 to view next page, press F4 to
page up, press F5 to page down, press F6 to exit.
5.3.2.4 View zones under test
This menu will show the list of zones which are under test mode. Note that a zone under test is not in service
for fire detection.
Press F1 to return to the first page, press F4 to page up, press F5 to page down.
5.3.2.5 View addresses linked to a zone
Press 5 to enter the sub-menu to view addresses of loop devices assigned under designated zone(s). Users
can either enter the number of the zone by pressing the numeric keypad or press F2 or F3 to change the
zone. To exit the current window press F6.
Once the correct zone the user desires to access has been entered, the list of devices assigned to this zone
is displayed by the format of: Loop number-Device address (range).
5.3.2.6 View zone status
Press 6 to enter the sub-menu to view the status of zones. In this sub-menu, all the zones that are registered
in the panel are displayed starting from zone 001 along with their status (Normal/Fault/Alarm).
Press F1 to review the first page, press F4 or F5 to page up or down through the list of zones, press F3 and
enter the zone number from numeric keypad to access the detailed information/data on a specific zone and
press F6 to exit.
In the single zone mode, the F1 will clear the selected zone, F2 or F3 will change the zone number, F5
confirms the numeric entry, F6 exits the sub-menu and F4 allows the selection of a batch.
In the batch mode, press F1 to jump to the first page, press F4 to page up the list and to page down to the
next page, press F5. To exit the current interface, press F6. To return to the single mode press F3.
5.3.2.7 View device status
Press 7 to enter the sub-menu to view the detailed status of devices. The information about the devices is
displayed as loop number-device number, zone number, status (Normal / Fault / Alarm) and device
description.
Press F1 to move back/return to the first page, press F2 to review the maintenance detail from the company
who carries out the maintenance work. Press F3 to enter sub-menu Single view mode, users can enter the
loop and address of interest manually from the numeric keypad. Under this sub-menu, by pressing either F2
or F3, user can change the address of the device. When pressing F4 Batch, users can view the status of
devices listed as a batch/group, to scroll to the previous page, press F4, to scroll down to the next page,
press F5. To exit the current interface, press F6.