Page 12
J-400
4. The electrical supply for this product must include a suitably rated
switch or circuit breaker to open all ungrounded supply conductors
to comply with Section 422-20 of the National Electrical Code/USA,
ANSI/NFPA 70. The disconnecting means must be readily accessible
to the spa’s occupant but installed at least 5 feet (1.5m) from spa
water.
5. The electrical circuit supplied for the spa must include a suitable
ground fault circuit interrupter (GFCI) as required by NEC Article
680-42/USA.
6. To gain access to the spa’s power terminal block, remove the screws
securing the cabinet panel on the side of the spa under the controls.
Then remove the four door screws for the small access door on the
control box (Figure A).
7. Select the power supply entrance you want to use (Figure A) and
remove the short cabinet panel from the front of the spa. Make sure
to install a 3/4" electrical fitting and conduit through the large opening
provided in the bottom of the control box so you can feed the cable
through to the terminal block.
8. Connect wires to the terminal block (Figures B-F, pages 13-15).
ALL WIRES MUST BE SECURELY CONNECTED or equipment
damage could result!
9. Install control access box door and reinstall the cabinet side panels.
Figure A
Equipment Area
2
2
5
6
6
8
7
6
3
1
Access Door
WARNING!
DONOT LOOK AT LIT BULB
SEVERE EYE DAMAGE
OR BLINDNESS CAN OCCUR
9
10
12
11
4
Note:
Equipment location (such as pumps, CLEAR
RAY
system, drain, heater etc.) varies
by model.
1. J-1000™ Control Box
2. Power Supply Entrance(s)
3. Jets Pump
4. Heater
5. Spa Drain Valve
6. Pump Drain Plugs(s)
7. Jets Pump
8. Filter/Circulation Pump
9. CLEAR
RAY
Water Purification
System
10. Electronic Ballast (For
CLEAR
RAY
System)
11. J-1000 Control Panel
12. QuickDrain™