background image

Thank you for purchasing an interSeptor sensor

Please use the following instructions to install the sensor

Sensor Installation Instructions

Temperature / Temperature & Humidity 

 

 Sensors

The temperature sensor and/or temperature / humidity sensor should be connected to the
interSeptor using the supplied black cable. Once you have located the sensor, plug one end
of the cable into the RJ45 socket of the device and the other end into one of the two “EMD”
ports on the rear panel of the interSeptor. The interSeptor will then auto-detect the presence
of the device. The  high  / low thresholds  and  the hysteresis level for the sensors can be
configured via the web browser interface.

GoProbe! Sensors

The GoProbe! sensors (security, voltage, water leak detection, dry contact, PIR, vibration and
smoke)   should   be   attached   to   the   interSeptor   via   the   GoProbe!   alarm   sockets   on   the
temperature and temperature / humidity sensors. The sensor contacts should be inserted and
screwed into either the left pair (first alarm) or right pair (second alarm) of GoProbe! sockets.

Security Sensor

The relevant alarm should be configured in the browser (through the EMD-1 or EMD-2 setup
screens)   to   be   either   “Normal   Close”   or   “Normal   Open”,   depending   on   the   sensors
deployment.

Voltage Sensor / PIR Sensor / Vibration Sensor

The relevant alarm should be configured in the browser (through the EMD-1 or EMD-2 setup
screens) to be “Normal Close”. When power is lost, movement detected or vibration sensed
the alarm will become ‘Active’.

NOTE:   The   LED   on   the   voltage   detector   does   not   indicate   status   and   should   therefore   be

ignored.

Water Leak Detector 

The relevant alarm should be configured in the browser (through the EMD-1 or EMD-2 setup
screens) to be “Normal Open”.
When water is detected along the sensor cable the interSeptor will be activated.
Please follow these instructions to install the leak detection system:

1. Lay out the sensor cable in its intended location, taking care to keep it free from oil

and grease and away from metal surfaces.

2. Fix the sensor cable using the cable clips. Please take care not to damage the sensor

cable when fixing the clips. DO NOT CUT OFF ANY SURPLUS CABLE. When fixing
cable clips, wear eye protection as hardened steel nails can fracture when hit.

3. To   test   the   system,   drip   a   small   quantity   of   water   onto   the   sensor   cable.   The

interSeptor alarm will activate within 10 seconds. Allow the cable to dry completely for
the alarm to deactivate.

Reviews: