The JA-120N BUS module for electric door locks  

The JA-120N BUS module for electric door locks 

1 / 2 

MLY57702 

The product is a component of the JABLOTRON 100 system. 

It serves for powering and controlling electric door locks 

 

and access control units from the system BUS. During lock 
operation the included batteries supply enough current to open 
an electric lock, during the leading edge of the current pulse.  
The JA-120N can be mounted practically in any place where  
it is difficult to install an external power supply to control  
an electric lock.  

This module reacts to control panel PG outputs or it can be 

activated by a release key connected to the IN terminal. 

 

The module is supplied inside a JA-190PL installation box. 

It should be installed by a trained technician with a valid 

certificate issued by an authorised distributor. 

Installation 

 

Figure 1:  1 – rechargeable batteries; 2 – DOOR output indicator,  

3 – JA-100 BUS activity indicator; 4 – IN input activation indicator;  

5 – LEARN (enrollment)/ tamper contact; 6 – BUS terminals;  

7 – input and output terminals (I/O) 

 
1.  We  recommend  removing  the  module’s  PCB  to  avoid 

unwanted  damage  during  installation.  Punch  the  holes  into 
the  JA-190PL  rear  plastic  part  for  cables.  Insert  the  BUS 
cables  and  attach  the  plastic  base  onto  the  required  place 
using screws. 

 

When connecting the module to the 
system BUS, always switch the power off. 

2.  Put  the  PCB  back  onto  the  plastic  base.  Connect  the  BUS 

wires  to  the  BUS  terminals  (6)  and  the  cables  for  door  lock 
control  to  the  I/O  terminals  (7).  Always  use  CC-01 
(Jablotron)  cable  for  connecting  to  the  control  panel.  For 
connection of the door lock or the external power supply use 
cables with an adequate cross-section.  

Terminal descriptions: 
DOOR  

+12V output for electric lock control 

COM, IN

 

Input terminals serving for activation by the 
release button (reaction NO/NC). 

GND  

Common terminal for an external power supply 
and for electric door lock control 

+12V  

Input terminal for an external power supply  
(the DE 06-12 is recommended)  

3.  Proceed  according  to  the  control  panel  installation  manual. 

Basic procedure: 
a.  When  the  system  has  been  turned  on  then  the  yellow 

LED (3) flashes and it indicates the module has not been 
enrolled to the system yet. 

b.  Using 

F-Link 

software, select the required position in the 

Devices

 window and launch enrollment mode by clicking 

on the 

Enroll

 option. 

c.  Press the 

LEARN/TAMPER

 

(5) button in the module – 

the module is thus enrolled to the system and the yellow 
LED indicator goes off. 

4.  Put the cover on the module. 

Setting the module properties 

The  module  properties  can  be  set  in  the 

Devices

  window  

of  the 

F-Link

  software.  When  at  the  module  position,  use  

the 

Internal settings

  option  to  open  a  dialogue  window  where 

you can set the following options: 

LED  indication

  –  Enable/disable  optical  indication  by  the  red 

LED (4) of triggering the IN input. 

DOOR  reacts  to  PG  status 

–  Determines  which  PG  output  

or outputs the module reacts to.  

Minimum  PG  switching  time 

–  Sets  the  minimum  switching 

time  of  the  DOOR  output  regardless  of  the  PG  output  impulse 
length. 

Maximum  PG switching time 

– Sets the  maximum switching 

time  of  the  DOOR  output  regardless  of  the  PG  output  impulse 
length.  When  the  IN  input  is  triggered  the  DOOR  output  
is always switched on for that predefined time. 

Note:

  the  minimum  switching  time  can´t  be  set  to  a  higher 

value  than  the  maximum  value.  The 

F-link

  software  adjusts  its 

offer of those parameters dynamically. 

IN input options: 
Disabled 

 

The  module  doesn´t  react  to  IN  input 
activation 

Manual control

  

Triggering  the  IN  input  switches  on  the 
DOOR  terminal  for  a  predefined  time 
according  to  the 

Maximum  PG  switching 

time

 

System

  

Triggering  the  IN  input  causes  the  control 
panel to react according to the reaction set 
at  the  module’s  position  in 

F-link

 

(Reaction column) 

IN input inverted:

 Determines the logic of the IN input NC/NO. 

The  input  is  not  balanced  and  is  set  to  NO  as  a  factory  default 
(option disabled). 

DOOR  input  inverted:

  This  option  inverts  the  logic  of  the 

DOOR output for e.g. reverse locks. When the option is checked 
and  the  input  is  in  standby  a  voltage  occurs  on  the  DOOR 
output.  

Note:

 for correct functioning it is necessary to power the module 

from an external power supply (for instance: the DE 06-12). 

Blocking the IN input by section:

  This  option  can  block  the 

IN  input  by  setting  the  section  to  which  the  module  has  been 
enrolled. The  option  is  only  available  if Manual control  of the IN 
input has been enabled.  

Function  button  during  communication  fault:

  This  option 

keeps  the  module  active,  with  backup  control  of  the  DOOR 
output  by  IN  input  triggering  when  communication  with  the 
control panel is lost. 

Unlock the IN input during a fire alarm:

  This  parameter 

unlocks the IN input during a fire alarm even though blocking the 
IN  input  by  the  section  has  been  enabled.  This  option  
is available only if the function 

Blocking the IN input by section

” 

is enabled. 

 

Triggered tamper:

  This  parameter  can  disable  the  tamper 

contact for cases when the module is going to be installed inside 
a different box or into a box with different tamper protection. 

 

Note: 

The  module  is  designed  for  use  with  very  high  quality 

NiMH  batteries  (purchase  code-BAT-1V2-NIMH)  in  a  positive 
operational  temperature  range.  NiMH  batteries  have  unsuitable 
behaviour  in  a 

negative  operational  temperature  range

  so  

in this case we recommend using NiCd batteries in the module.

 

 

Application recommendation:

  

We  recommend  using  the  module  with  door  locks  complying 

with the following parameters:  
-  

Standard locks 12 V DC / max. 300 mA  

-  

Reverse locks 12 V DC / 170 mA (for reverse door locks it is 

necessary

 to plug in  an  external power supply, for  example 

the DE 06-12) 

 
Accumulators lifetime (approximate values) 

 

Electromagnetic 

lock current 

consumption 

(mA) 

Duration of 
an impulse 

(s) 

Period of time 

necessary to 

recharge 

accumulators after 

one activation (s) 

Number of 

impulses from 

fully charged 

accumulators 

(1900mAh) 

 

230 

10 

387 

618 

230 

10 

193 

1241 

230 

10 

55 

3114 