background image

AC-8014/814 receiver 

1 / 1 

MJQ51505 

The AC-8014/814 receiver

The AC-8014 is a 14-channel receiver of signals from TP-8x wireless 

thermostats working on a frequency of 868 MHz. It can also be used 
with TP-8x digital bus thermostats. The AC-8014 can efficiently control 
multi-zone heating (including thermoelectric actuating valve-drivers to 
replace thermostats on radiators) or cooling systems. The receiver has 
a special MODE channel which turns the heating to economy mode. It is 
designed for heating system control and is not suitable for extending 
hardwired alarm systems via wireless detectors. 

Due to the maximum current limits of the outputs, pulses switching the 

outputs off for short moments are used (when more then 8 outputs are 
used). Therefore the AC-8014 should only be used with thermoelectric 
actuating valve-drivers. It should not be used to control any relays, 
semiconductor switches etc. LEDs on the receiver’s front cover indicate 
the status of each output channel.  

The AC-8014 can be considered a hybrid of two components: the 

AC-814 digital bus receiver and the wireless module. The AC-814 only 
allows connection by digital bus and can be supplied standalone as a 
cut-down variant of the AC-8014. 

The AC-8000R built-in power relay module can be used as a pump 

control. A second AC-8000R module can be plugged-in to provide boiler 
control. Both relays work with OR logic: they are switched if any of the 
1–14 outputs is activated. 

 Installation 

Attach the unit to the desired location with three screws. Route all the 

cables to the unit before you tighten the case. 

Fix the cables firmly inside the box by a sliding strap. 

Note: Only a qualified technician should provide installation and 
servicing. The user is not allowed to open the cover and/or make 
any modifications. The mains cable must also be fixed outside the 
receiver’s case. Replace the mains plug if necessary for your 
country. 

 

Terminal description: 

AC, AC

  

– power input 24 V AC. 

SUM (summer) 

– input terminal. When switched to ground, economy 
mode is activated. This is indicated by the MODE 
channel LED lighting. 

FRE (freeze) 

– output terminal. If any of the thermostats sends a 
signal about the temperature being under the value 
of the ALLo (critically low temperature) parameter in 
the thermostat, this terminal switches to ground for 

10 seconds

. The terminal’s maximum load is 

100mA. 

BUS,BUS  

– 

terminals for the digital bus connection (for 

thermostats of the relevant type). Maximum length 
of the connection cable is 200m. 

1–14 

– channel  outputs,  switchable  to  ground.  The      
AC-8014 has pulsed switching. 

COM

  

– common positive output terminals 24V DC. 

 

Terminals of the AC-8000R power module: 

L_A, N_A, PE_A 

– power supply input for the circulatory pump or 
boiler (use an external fuse for its protection). 

L_B, N_B, PE_B 

– 

terminals for the circulatory pump or boiler 

connection (the L_B terminal is triggered if any of 
the 1–14 outputs are switched on). 

The receiver is protected against shorts on the output. If the output is 
overloaded (the current is greater than 0.4A), then the output is 
automatically disconnected. A fault is indicated by rapid red flashing 
of the corresponding LED indicator. The output is under constant 
monitoring and when the output current decreases below 0.4A the 
output will be switched on again. 

If it is necessary to have more channels, then it is possible to 

connect another unit via a 4-wire cable connected to terminals 1–4. In 
this case a single wireless unit should be shared by both receivers. 
However, each receiver only controls its own built-in AC-8000R 
module. 

There is an available connector for an external antenna (e.g. AN-80 

or AN-81) on the bottom side of the front housing. If the external 
antenna is used no further modifications to settings or connections 
are necessary. 

 

Fuse T 400 mA

P

B

L_B

N_B

PE_B

L_A

N_A

PE_A

Second

 module

connection

 8000R

Built-in 8000R module

Antenna connection

SUM
 FRE
GND

1
2
3
4

Terminals for
auxiliary signals

Wireless module

Terminals for
digital bus thermostats

Terminals for multiple
 AC-8014 wiring

Connecting cable

Pump module connection

Boiler module connection

Terminals 24 V AC

Fuse box
Fuse 3.15A

Channels 1-14
output terminals

Power supply

 

 

 

 