background image

 

PR_I017/2023-01-23-EN

 

 

11

 

INSTALLATION 

If  this  room  heater  is  not  properly  installed,  a  house  fire  may 
result.  To  reduce  the  risk  of  fire,  follow  the  installation 
instructions.  Contact  local  building  or  fire  officials  about 
restrictions and installation inspection requirements in your area. 
 
WARNING  ALWAYS  USE  J.A.  ROBY  PARTS  on  your 
appliance.  Using  other  differences  parts  can  damage  the 
appliance and cause injury. 

 

Use  of  smoke  detectors  and  carbon 
monoxide monitors 

To  provide  reasonable  fire  prevention,  the  following should  be 
given serious consideration: 

1.  At  least  one  smoke  detector on  each  floor of  your  home 

should be installed to ensure your safety. They should be 
located away from the heating appliance and close to the 
sleeping areas. Follow the smoke detector manufacturer’s 
placement  and  installation  instructions,  and  be  sure  to 
maintain regularly. 

2.  A conveniently located Class A fire extinguisher to contend 

with small fires resulting from burning embers. 

3.  A  CO  detector  should  be  installed  in  the  room  with  the 

appliance. 

4.  A  practiced  evacuation  plan,  consisting  of  at  least  two 

escape routes. 

5.  A plan to deal with a chimney fire as follows:  

a. In the event of a chimney fire:  

b. Evacuate the house immediately 

c. Notify fire department. 

 

The average of the CO emission (carbon monoxide) is 100.4 
g/hr. To maintain this rate, it’s recommended to operate the 
appliance in low or medium burn rate. 

The hazards with some fuels (e.g. Charcoal) and possibilities 
of generating carbon monoxide and the hazards from carbon 
monoxides. 

When the smoke detector is activated is mean that the 
smoke spill out of the appliance. Verify the door is close 
and the draft in chimney is good. 

 

Floor protection 

Your stove must be installed on a non-combustible material 
plate to protect the floor and avoid fire caused by:  

 

Projections of sparks when opening door or loading 
logs; 

 

The heat radiation from stove runaway which might 
cause an auto-ignition to the floor and the coating; 

 

Flow of creosote when there is a fire chimney. 

The  coating  used  for  the  protection  must  be  non-combustible 
and  approved  according  to  standard  UL1618  for  USA  or 
approved to the locals codes (Example: cement, brick, ceramic 
tiles, etc.) 

HORIZONTAL VENTING MANDATORY

 Non-combustible floor 

protections  must  extend  beneath  the  flue  pipe  when  installed 
with  horizontal venting  and  it should extend 2  inches  (51  mm) 
beyond each side of the pipe. 

You  can  extend  the  protection  plate  while  respecting  the 
clearances of each side of stove.   

Floor protection plate minimum dimensions 

The  following  dimensions  are the minimums values  and  it can 
be higher. 

Canada: 
 

  41 inches (104 cm) 

  54 inches (137 cm) 

  3/8 inch thick (1 cm)  

 
United States: 
 

  41 inches (104 cm) 

  52 inches (132.1 cm) 

  3/8 inch thick (1 cm) 

 

 

Clearances of the stove until the floor plate 
protection 

The following dimensions are the minimums values and it can 
be higher. 

Canada: 
 

  8 in (20.3 cm) behind 

  8 in (20.3 cm) beside 

  18 in (45.7 cm) in front of the door opening.  

 
United States: 
 

  8 in (20.3 cm) behind 

  8 in (20.3 cm) beside 

  16 in (40.64 cm) in front of the door opening. 

 

 

Summary of Contents for PIONEER

Page 1: ...T RESTRICTION AND INSTALLATION INSPECTION IN YOUR AREA Instruction Manual PLEASE READ CAREFULLY AND KEEP THIS MANUAL FOR FUTURE REFERENCE 490 rue de l Argon Qu bec CANADA G2N 2C9 T l 418 849 8095 Fax...

Page 2: ...nstallation 21 Transportable building installation 22 Chimney installation General steps 23 Inside Masonry Chimney Vertical Installation 24 Outside Vertical Installation 24 Cathedral Vertical Installa...

Page 3: ...d on the floor Do not install in a sleeping room Exterior air inlet is mandatory for mobile home use All roof chimney termination shall be able to be readily removed at or below an elevation of 13 1 2...

Page 4: ...PR_I017 2023 01 23 EN 4 RATING PLATE...

Page 5: ...PR_I017 2023 01 23 EN 5 APPLIANCE DIMENSION...

Page 6: ...PR_I017 2023 01 23 EN 6...

Page 7: ...PR_I017 2023 01 23 EN 7...

Page 8: ...cm Exterior Depth 33 5 8 in 85 6 cm 33 5 8 in 85 6 cm 34 1 4 in 87 cm 33 5 8 in 85 6 cm Door Opening 15 1 8 in x 9 1 4 in 38 4 cm x 23 5 cm 15 1 8 in x 9 1 4 in 38 4 cm x 23 5 cm 15 1 8 in x 9 1 4 in...

Page 9: ...ior Depth 33 5 8 in 85 6 cm 34 3 8 in 87 3 cm 34 3 8 in 87 3 cm 36 1 4 in 91 9 cm Door Opening 15 1 8 in x 9 1 4 in 38 4 cm x 23 5 cm 15 1 8 in x 9 1 4 in 38 4 cm x 23 5 cm 15 1 8 in x 9 1 4 in 38 4 c...

Page 10: ...m 16 inches 40 6 cm Front 48 inches 121 9 cm 48 inches 121 9 cm 48 inches 121 9 cm 48 inches 121 9 cm Minimum Ceiling height 84 inches 213 4 cm 84 inches 213 4 cm 84 inches 213 4 cm 84 inches 213 4 cm...

Page 11: ...fuels e g Charcoal and possibilities of generating carbon monoxide and the hazards from carbon monoxides When the smoke detector is activated is mean that the smoke spill out of the appliance Verify...

Page 12: ...for a stove with side shield is 16 inches 40 6cm and for a stove without side shield the clearance is 23 inches 58 4 cm For a 45 corner or other corner installation the minimum clearance between the...

Page 13: ...rated and secure it with nut lock washer and washer 2 3 4 Attention Be sure the legs are in place correctly positioned and in contact with the bottom of the stove Fan and Snap disc box installation Th...

Page 14: ...ONT OF THE APPLIANCE When it s ON the snap disc will start at the moment when the temperature of ventilation box gets 120 Fahrenheit 49 Celsius DO NOT CONNECT TO OR USE IN CONJUNCTION WITH ANY AIR DIS...

Page 15: ...ke double pipe For the smoke simple pipe it s not necessary to remove the pre cut metal part For the double smoke pipe you need to remove the pre cut metal part See blue arrow below Put the smoke pipe...

Page 16: ...firebrick installation Put 8 bricks A on the back wall and fix with a screw and brick support Floor firebricks installation Put 4 Bricks A near to the back wall and 2 bricks P in front of bricks A Fl...

Page 17: ...eel parts on the rockwool as illustrated 1 Put 3 A bricks over the two top pipes and push them against the back bricks Be sure to eliminate any space between the back bricks and the bricks you install...

Page 18: ...ration and parts without ash plug 1 2 half disk metal steel plates 2 1 rock wool insulating blanket 3 3 3 4 x 15 pipes with holes on a single side 4 2 3 4 x 15 pipes with bigger holes on both side 5 1...

Page 19: ...d list of parts with ash plug 1 2 half disk metal steel plates 2 1 rock wool insulating blanket 3 3 3 4 x 15 pipes with holes on a single side 4 2 3 4 x 15 pipes with bigger holes on both side 5 1 scr...

Page 20: ...nce by a certified installer Note This appliance have to be connected to 6 inches 15 24 cm factory build chimney HT UL 103 or CAN ULC S629 compliant or a 6 inches 15 24 cm masonry chimney with a homol...

Page 21: ...earances and inclinations of the horizontal sections and verify if you have all the necessary parts for the final installation o For direct vertical installation you will need 1 vertical section of 24...

Page 22: ...stance of 4 inches 10 2 cm or more in order to avoid contact with chimney f The chimney must exceed at least 3 feet 91 4 cm from the highest point of opening made in the roof and exceed also 2 feet fr...

Page 23: ...installation method Always refer to the manufacturer s manual of the chimney for a more detailed method for your chimney 1 Determine the total length needed for your chimney 2 Cut the holes into all...

Page 24: ...re of the manner you have to To install the stove onto an abandoned masonry fireplace and use the good condition masonry chimney the chimney must have inside a certified metallic sleeve cover up all t...

Page 25: ...e with the applicable local laws or the CAN CSA B365 NFPA211 USA norms Follow the chimney manufacturer s instructions to install the chimney Always pass chimney between joists If a joist need to be cu...

Page 26: ...certified Installer Always frame around chimney Keep minimal clearances written into your chimney manual Do not fill the gap between the fire stop and the chimney Nothing must be in contact with the c...

Page 27: ...ntake box Insert the pipe into the hole and screw the pipe using the 3 holes in the tabs Put a generous layer of high temperature latex caulking onto the joint to ensure the pipe is sealed 2 Cut the e...

Page 28: ...re 2 type of tubes used into the stove Three of them are single side perforated 1 and are in the back of the heat chamber The 2 tubes in front of the heat chamber are double side perforated tube 2 How...

Page 29: ...O Disc Low burn rate From the high burn rate coal bed when 5 to 6 lbs left the load can be inserted in the firebox Open the door Insert the 36 lbs 16 3 Kg load in the wood heater Close the door immedi...

Page 30: ...rewood over the ember keeping it away from the glass door to avoid flame touching the ceramic glass ATTENTION DO NOT OVER CHARGE THE STOVE OVER THE UPPER BRICK DO NOT BUILD A FIRE NEAR THE WINDOW THIS...

Page 31: ...ent draft will cause the appliance to leak smoke into the room through appliance and chimney connector joints MAINTENANCE Ash Removal The wood burning doesn t transform the wood into combustion gas co...

Page 32: ...ng chimney also requires to climb on the roof to remove the chimney cap and sometime even a very high chimney section too We recommend to call a Professional chimney Sweeper certified by APC in Quebec...

Page 33: ...m braided fiberglass rope To install the new fiberglass rope we recommend to detach the door from the stove Please see the pertinent section in this manual Fiberglass rope preparation 1 Take the end o...

Page 34: ...PR_I017 2023 01 23 EN 34 ANNEX 1 Exploded diagram of door Arc door...

Page 35: ...PR_I017 2023 01 23 EN 35 ANNEX 2 Fans electric wiring diagram...

Page 36: ...3 Parts that can be replaced Bricks Door glass Spring Handle Stove Door with handle Fans Flat fiber glass rope around glass Round fiberglass rope Ash Plug Slotted Brick Washer Call your stove seller...

Page 37: ...t or unit after inspection and investigation of the defect The manufacturer may at its discretion fully discharge all obligations with respect to this warranty by refunding to the original warranted p...

Reviews: