Operation: CP1S Version
20
CENTRON® Polyphase Meter Technical Reference Guide
Non-Detented Register
The Non-Detented Register displays the delivered energy plus received energy.
kWh
V
A
V
B
V
C
Figure 13: Non-Detented Register (kWhd + kWhr)
Detented Register
The Detented Register addresses applications requiring the reading of delivered kWh only.
Received energy is discarded.
DET
kWh
V
A
V
B
V
C
Figure 14: Delivered kWh with Detent Enabled (kWhd)
Net Register
The Net (kWh) Register addresses applications requiring residential net metering points. Net
kWh is the delivered kWh to the customer minus any received kWh from the customer.
NET
kWh
V
A
V
B
V
C
Figure 15: Net kWh (kWhd - kWhr)