background image

Regenerative Power System

IT-M3600 Series User Manual

Model: IT-M3600 Series

Version: V1.0/04,2020

Summary of Contents for IT-M3600 Series

Page 1: ...Regenerative Power System IT M3600 Series User Manual Model IT M3600 Series Version V1 0 04 2020...

Page 2: ...that conflict with these terms the warranty terms in the separate agreement shall prevail Technology Licenses The hardware and or software de scribed herein are furnished under a li cense and may be...

Page 3: ...ice must be shipped PRE PAID And ITECH will pay for return of the product to customer If the product is returned to ITECH for warranty service from overseas all the freights duties and other taxes sha...

Page 4: ...refer to this manual for specific Warning or Caution information Negative terminal A chassis terminal Safety Precautions The following safety precautions must be observed during all phases of opera ti...

Page 5: ...ing the instrument to power supply Ensure the voltage fluctuation of mains supply is less than 10 of the working voltage range in order to reduce risks of fire and electric shock Do not install altern...

Page 6: ...must al ways be protected from electric shock Ensure that the electrodes are either insulated or covered using the safety covers provided so that no accidental contact with lethal voltages can occur N...

Page 7: ...product complies with the provisions of all rel evant European laws if the year is shown it indicates that the year when the design is approved This instrument complies with the WEEE directive 2002 9...

Page 8: ...mplies with tag re quirements of the WEEE directive 2002 96 EC This tag indicates that the electronic equipment cannot be disposed of as ordinary household waste Product Category According to the equi...

Page 9: ...IEC 61000 3 2 2018 RLV IEC 61000 3 3 2013 A1 2017 IEC 61000 4 2 2008 IEC 61000 4 3 2006 A1 2007 A2 2010 EN 61000 4 3 A1 2008 A2 2010 IEC 61000 4 4 2012 IEC 61000 4 5 2014 A1 2017 IEC 61000 4 6 2013 co...

Page 10: ...Device Under Test DUT 24 2 7 Connect the Communication Interface 27 2 7 1 USB Interface 28 2 7 2 GPIB Interface 29 2 7 3 LAN Interface 30 2 7 4 RS 232 Interface 36 2 7 5 RS 485 Interface 38 2 7 6 CAN...

Page 11: ...e and Recall Operations 97 6 3 Local Remote Mode Switch 99 6 4 Basic Operation 99 6 4 1 Set the Beeper Status 99 6 4 2 Set the Power on State 100 6 4 3 Set the Sense Function State 100 6 4 4 Set the C...

Page 12: ...Manual 10 5 IT M3623 152 10 6 IT M3633 157 10 7 IT M3614 161 10 8 IT M3624 166 10 9 IT M3634 171 10 10 IT M3615 178 10 11 IT M3625 182 10 12 IT M3635 187 11 Supplemental Characteristics 193 A Appendix...

Page 13: ...ive electronic load When being used as a load its energy recovery function can convert the absorbed DC power into AC power and return it to the local grid When being used as a power supply it is a wid...

Page 14: ...alize reliable grid connection Parallel up to 16 units Independent control of multi channels implement synchronization or proportional tracking sense abnormal protection Temperature measurement functi...

Page 15: ...es based on selected function 5 Function keys group Refer to 1 3 Keyboard Introduction for the detailed description about the function keys 6 Push on knob Rotate the knob to adjust the setting values...

Page 16: ...when the instrument in single mode pressing the key also can switch to CV mode I set Set the current value Source mode In CV priority press I set and enter the current value setting state Repress I se...

Page 17: ...ted and then press the function key the detailed functions are listed as follows Keys Description Shift V set Config Enter the Config menu Used to set the configuration parameters The configuration pa...

Page 18: ...scriptions of the rear panel are shown as below No Name Description 1 DC terminals DC DC output input terminals and ground terminals used to connect DUT 2 Protective cover Protective cover for DC term...

Page 19: ...home Screen displayed information is different under Source mode and Load mode The screen information displayed as below Under Source mode No Name Description 1 Output Voltage Displays the present ou...

Page 20: ...ad mode No Name Description 1 Output Voltage Displays the present output voltage value 2 Output Current Displays the present output current value 3 Output Power Displays the present output power 4 Vol...

Page 21: ...e Time Current rising time When select CC priority the menu shows the two items I Fall Time Current falling time Output R Set the internal resistance On Delay Set the output on delay time Off Delay Se...

Page 22: ...Press Enter on a menu interface to enter the setting interface Press Esc to return to the previous menu The instrument return to home screen automaticly when no action in a long time The description o...

Page 23: ...LAN LAN communication interface Lan Info View the LAN information Status IP Mode Status IP Addr Sub Net Gateway DNS1 DNS2 MAC Addr MDNS Status Host Name Host Desc Domain TCPIP INSTR Socket Port Lan Co...

Page 24: ...ommunication interface Display as the following format baud rate_data bit_ parity bit_stop bit Select the baud rate from the following options 4800 9600 19200 38400 57600 115200 The data bit parity bi...

Page 25: ...r which slave belongs to Master Set the instrument to master mode Master group Specify the master group the range from A to P Master Total Set the total instrument number of the same group within the...

Page 26: ...rical regenerative power and capacity information UUT Temp DUT temperature Re Energy The regenerative power AHour capacity of charge and discharge when the battery simulator function or battery test f...

Page 27: ...400 IT M3633 12 800 IT M3614 300V 6 200 IT M3624 6 400 IT M3634 6 800 IT M3615 600V 3 200 IT M3625 3 400 IT M3635 3 800 Optional accessories You can purchase accessories for the IT M series of instrum...

Page 28: ...wing optional accessories from ITECH are sold separately Users need to purchase separately Device Name Model Description Type GPIB communication interface IT E1205 When the user needs to use GPIB inte...

Page 29: ...ble remote operation this option is the right choice Optional Anti reverse connection module IT E118 Connecting to DC and sense terminals for reverse connection protection When the user needs to conne...

Page 30: ...the communication card and analog card you must re start the instrument It takes about 30 seconds for the instrument to automatically update the communication board before it is ready for use Copyrig...

Page 31: ...nstrument immediately Table 2 1 Package box contents Item Qty Model Remarks regenerativ e power system IT M3600 series This series include 1 8 Models and Options Power Cord X 1 User may select an appr...

Page 32: ...d and rational sized space Please select appropriate space for installation based on the instrument size The detailed dimension drawings of theIT M3600series are as follows Unit mm allowable deviation...

Page 33: ...rchitecture the instruments can be directly and easily stacked on the desk without purchasing any accessories A maximum of 10 instruments can be stacked The stacking schematic diagram is as shown belo...

Page 34: ...ive grounding Do not use terminal board without protective grounding The instrument rear panel provides a separate screw used for chassis ground Please make proper connections In the event of a failur...

Page 35: ...ut Option Opt 01 220 240VAC 10 47 to 63 Hz Option Opt 02 100 120 VAC 10 47 to 63 Hz Connecting the Power Cord To connect the power cord 1 Make sure that the front panel power switch is in the OFF posi...

Page 36: ...Off position otherwise touching the output terminals on the rear panel may result in personal injury or death due to electric shock To avoid electrical shock before testing please make sure the ratin...

Page 37: ...d and black test cables to the output terminals and connect the ground terminal correctly Re tighten the screws When maximum current that one test cable can withstand fails to meet the rated current u...

Page 38: ...cables to the output terminals and connect the ground terminal correctly Re tighten the screws When maximum current that one test cable can withstand fails to meet the rated current use multiple piece...

Page 39: ...communication card installation slot is on the rear panel of the instrument User can install it directly after purchasing the communication card The instrument must be power off when install or remov...

Page 40: ...d alone USB interface IT E1209 or USB LAN interface IT E1206 the following can help users quickly understand the steps required to connect the USB interface The figure below shows a typical USB interf...

Page 41: ...PIB Interface When the optional interface card is a GPIB interface IT E1205 you need to know the following Each device on the GPIB IEEE 488 interface must have a unique number address between 0 and 30...

Page 42: ...n be used to connect directly to the computer via the LAN interface Connect to the site LAN A site LAN is a local area network in which LAN enabled instruments and computers are connected to the netwo...

Page 43: ...nd the DHCP server will assign an IP address Subnet Mask and Default Gateway to the instrument If a DHCP server is unavailable the instrument will try to obtain an IP address using AutoIP AutoIP autom...

Page 44: ...DNS2 This field enters the standby address of the server Contact your LAN administrator for server details The same numbering notation applies as for the IP Address A value of 0 0 0 0 indicates that...

Page 45: ...ace 2 Use left and right keys or rotate the knob to select I O Config and press Enter key to confirm 3 Use left and right keys or rotate the knob to select LAN and press Enter key to confirm 4 Use lef...

Page 46: ...rm User need to set the Socket Port when enable the Raw Socket service 7 Rotate the knob to adjust the parameter and press Enter key to confirm On enable the service Off disable the service 8 After se...

Page 47: ...es by clicking the seven buttons shown in the navigation bar on the left side of the window The detailed descriptions are as follows Home Web home interface displays the model and appearance of the in...

Page 48: ...th a newline 2 7 4 RS 232 Interface When the optional interface card is RS232 CAN interface IT E1207 the following can help users quickly understand the steps required to connect the RS 232 interface...

Page 49: ...are as follows 1 Press Shift P Set System to enter into the system menu interface 2 Use left and right keys or rotate the knob to select I O Config and press Enter key to confirm 3 Use left and right...

Page 50: ...ce converter to connect to your computer according to the actual situation for example RS 485 to RS 232 interface device or RS 485 to USB interface device Etc the RS 485 to USB interface device is tak...

Page 51: ...5 After finishing the setting press Esc to exit 2 7 6 CAN Interface When the optional interface card is RS232 CAN interface IT E1207 the following can help users quickly understand the steps required...

Page 52: ...50K 4 Use left and right keys or rotate the knob to select Baud rate and press Enter key to confirm Address 1 5 Rotate the knob to set the communication address and press Enter key to confirm 6 After...

Page 53: ...Inspection and Installation The connection diagram of multiple devices is as below Copyright Itech Electronic Co Ltd 41...

Page 54: ...ent electric shock and damage to the instrument please observe the following precautions Before connecting power cord be sure to confirm that the power voltage matches with the supply voltage Be sure...

Page 55: ...el Press the Esc button to try to clear the current fault status The user can also restart the instrument to try to clear the fault status Wait until the power is turned off and then start again If th...

Page 56: ...ch as the POWER switch and the internal input fuses 3 2 Source Mode Load Mode Switch This series Regenerative Power System can be used as a bipolar power supply or a load which can be switched by Sour...

Page 57: ...the user selects the Running mode on the front panel the instrument inter face displays the parameters to be set under the existing running mode and the cursor flashes for prompt Or press the knob to...

Page 58: ...OPP UUT OTP UCP UVP The parameters displayed in the source mode and load mode are different Functionmenu includes output input list and so on The parameters displayed in the source mode and load mode...

Page 59: ...does not guarantee that the outputs are powered off if a hardware or software fault occurs See the cautions about connecting the test lines before connecting test lines You can press the On Off key o...

Page 60: ...age at its programmed setting as long as the load current remains within the positive or negative current limit settings Current priority mode keeps the output current constant In current priority mod...

Page 61: ...Note that when the output current reaches either the positive or negative current limit the unit no longer operates in constant voltage mode and the output voltage is no longer held constant Instead t...

Page 62: ...voltage is higher than the voltage limit setting of the instrument Once the current exceeds the built in negative over current limit the output will shut down In such a case it is important to set the...

Page 63: ...This series instrument is supported setting the V Rise Time V Fall Time under CV priority mode and I Rise Time I Fall Time under CC priority mode The slope is the time for one voltage current point to...

Page 64: ...f battery in battery simulation test and it can simulate the real working state of many kinds of batteries accurately The steps of setting as follows 1 Press Shift V set Config to enter the Config men...

Page 65: ...switch Recall Recall and view List files Recall List 1 10 Select the number of the recalled List file List Setup View the attribute parameters of List file which shall be consistent with List Setup e...

Page 66: ...tion is finished Repeat Set the number and range of running cycles of the List file 1 65535 Edit Step Edit the step parameters of List file Current Voltage Current value voltage value Based on the sel...

Page 67: ...r setting For detailed information about List file editing recalling and running please refer to the specific introduction below The running recalling and editing of List function are mutual prerequi...

Page 68: ...cannot select the number of step to be edited and can only start ed iting from step 1 If the existing List file is an existed file display Edit Step 1 6 The user can select the number of any step for...

Page 69: ...he Edit menu to select the corresponding file number for editing 1 List Setup 2 View Step 1 6 4 Rotate the knob select List Setup and press Enter key for confirmation Rotate the knob to view the attri...

Page 70: ...top existing test and turn off the List function Or press Reset to restart a new test 4 2 2 Battery Charging Discharging Test Function This series provides the battery charging and discharging test fu...

Page 71: ...rn to the main interface if there is no operation for a long period operation steps 1 Under source mode press Shift I set Function to enter into the function menu interface 2 Rotate the knob to select...

Page 72: ...umber of List file to be recalled A maximum of 10 battery test files can be recalled in this instrument Recall Batt 1 10 When the selected number is empty the interface would prompt that the recalled...

Page 73: ...the battery based on needs for true emulation of various states of the battery to meet various test requirements of the user During the emulation of charge and discharge test functions of the battery...

Page 74: ...on the emulation battery specification Full Volt Battery voltage value under full state Empty Volt Battery voltage value under empty state Inner R Battery internal resistance value Capacity Battery ca...

Page 75: ...3 Edit the following parameters of this battery emulation file in successive Press Enter key to confirm setting 1 Cell Properties 2 Parallel 1 3 Series 1 4 I_Limit 2 00A 5 I_Limit 2 00A 6 EXIT Cell Pr...

Page 76: ...user can view the setting information of the existing battery emulation file The following parameters can only be viewed and cannot be edited To modify them please return and enter the Edit menu to se...

Page 77: ...e maximum power point tracking MPPT mechanism built in and it is very important to test the efficiency of this MPPT The PV array module cell is a device that converts from light energy to electric ene...

Page 78: ...Set the open circuit voltage value Imp Set the maximum power current value Vmp Set the maximum power voltage value Isc Set the short circuit current value Table Indicates a user defined 1024 point I...

Page 79: ...ress Enter Also you can set the filter speed in SAS Filter according to the ac tual test needs After the above Curve parameters are set completely you can press Esc until you return to the SAS main in...

Page 80: ...the Curve file to be run 2 Set the Vmax in Config menu and Filter as the actual test needs 3 Press the Left Right key on the SAS main interface to select Run and press Enter At this point the instrume...

Page 81: ...e descriptions of protect menu are listed in the table below Protect Protection function menu OVP Over voltage protection Off Turn the OVP function off On Level Over voltage protection point Delay Del...

Page 82: ...Protect to enter Protect menu interface 2 Rotate the knob to select OVP and press Enter key to confirm 3 Rotate the knob to select On and press Enter key to confirm 4 Rotate the knob to adjust the ov...

Page 83: ...over current and possibly damaged due to an excessive current An over current protection will occur if Enable OCP The output current value is greater than the set current protection point Level and th...

Page 84: ...n Over power protection function allows the user to enable the protection and set a over power limit Level and delay time Delay This function prevents the output power from being higher than the limit...

Page 85: ...d the protection fault Press Esc key or send the command PROTection CLEar to clear the protection status The Over Power Protect displayed in front panel is cleared and the instrument exits OPP status...

Page 86: ...under current protection occurs the instrument responds as follows Instrument output is off The buzzer sounds The interface displays Under Current Protect and flashes Status register the UC status bit...

Page 87: ...rotection In most cases these momentary conditions would not be considered an under voltage protection fault and having an UVP condition disable the output when they occur would be a nuisance Specifyi...

Page 88: ...tate the knob to select CC or CV and press Enter key If CC is selected it indicates that the instrument triggers protection when the running mode is switched to CC mode If CV is selected it indicates...

Page 89: ...tage and recover to normal running state please delete the conditions leading to protection fault Press Esc key or send command PROTection CLEar to clear the protection state The Foldback Protect on t...

Page 90: ...nstant current CV constant voltage CP constant power CR constant resistance Complex operation modes CV CC CV CR CC CR CV CC CP CR The procedures to select the operation mode are as follows 1 Press Shi...

Page 91: ...ode When select CC CV CP CR modeUnder load mode the instrument operating in present mode This series electronic loads operate in constant voltage current resistance or power modes to satisfy a wide ra...

Page 92: ...figure When the UUT is a battery the electronic load changes to simulate device loading behavior Many battery discharge applications and power consumption profiles can be simulated for analysis makin...

Page 93: ...test the charging station or the car charger When the CV is working the maximum loading current is limited Under this mode the load can automatically switch among CV CR CC and CP modes It is suitable...

Page 94: ...his moment the V set key lights up The user can set the existing voltage value of the battery When the load is under the battery simulation mode the loaded current limit is the maximum current value o...

Page 95: ...ob to set the delay time and press Enter to confirm 4 Press Esc to exit 5 1 7 Enable the Input User can press On Off key on the front panel to control the instrument input When receive the On Off comm...

Page 96: ...recalled List file List Setup View the attribute parameters of List file which shall be consistent with List Setup edited in the Edit The attribute parameters can only be viewed and cannot be modifie...

Page 97: ...ting for Step1 Range 0 001S 3600S Next Select whether to edit the next step Yes No Insert Step Insert steps before each specified step Add Step Add steps after each specified step Delete Step Delete t...

Page 98: ...nd press Enter key for confirmation Set the attribute parameters of the List file in successive The setting method for each item is the same Select one item and press Enter key for confirmation When t...

Page 99: ...bute values to system default values When No is selected do not clear steps Copy File 1 to 2 Execute this step and copy existing List 1 file to List 2 file Recall and view List files If several List f...

Page 100: ...he running 1 Select the List file to be run in the Recall List 2 In the List function setting interface select Run and press Enter key to confirm that the instrument automatically returns to the main...

Page 101: ...number Disch I Set the discharging current Disch Time Set the discharging time Cut Off V Set the cut off voltage Cut Off I Set the cut off current Cut Off Q Set the cut off capacity Edit Edit the bat...

Page 102: ...ry test file it is necessary to edit battery test file recall battery test file and finally run the recalled battery test file Edit Battery Test File 1 Under the battery test interface select the Edit...

Page 103: ...g time and battery capacity When testing as long as any one of the cut off conditions is met the test stops Stop running and re running During the running of battery test file press Shift I set Functi...

Page 104: ...voltage value If not necessary do not set the loading voltage to prevent unnecessary trouble from failure of loading If the instrument can not load please firstly check whether the VON function is se...

Page 105: ...otection Function 5 3 1 Set Over Current Protection OCP Users can enable the OCP function and set the protection limit Level and protection delay time Delay When the current i e the Meter value is gre...

Page 106: ...tection occurs the instrument responds as follows Instrument input is off The buzzer sounds The interface displays Over Current Protect and flashes Status register the OC status bit is set to 1 To cle...

Page 107: ...PP delay time has expired and the over power condition persists the output will shut down Clear Over Power Protection When over power protection occurs the instrument responds as follows Instrument in...

Page 108: ...having an UVP condition disable the output when they occur would be a nuisance Specifying an UVP delay lets the UVP circuit ignore these momentary changes during the specified delay period Once the UV...

Page 109: ...the front panel display a key symbol All panel keys are locked except for On Off Shift Enter Lock keys You can repress Shift Enter Lock to unlock the front panel 6 2 Save and Recall Operations The pow...

Page 110: ...tion mode and level You can do the save and recall operations by the following two methods Press the composite keys Shift Save to save the parameters Press the composite keys Shift Recall to recall th...

Page 111: ...except for the On Off and Shift Link Local keys are locked You can press Shift Link Local to switch the remote control to local control The mode modification will not affect the output parameters of t...

Page 112: ...he same settings as last time you turned off but the output state is OFF state 4 Press Esc to exit menu interface 6 4 3 Set the Sense Function State This menu item is used to switch the instrument to...

Page 113: ...igger source Bus Select the remote interface command as the trigger source such as the TRG command The procedures to set the menu item are as follows 1 Press Shift P set System to enter the system men...

Page 114: ...00S Off Delay 0 000S Output R 0 0m Config Menu Load Mode Mode CC I Rise 1 0A ms I Fall 1 0A ms On Delay 0 000S Off Delay 0 000S Von Level 0 1 Von Mode Latch System Menu Beep On PowerOn Reset Sense Off...

Page 115: ...UCP Mode Off UCP Level 0 000A UCP Delay 10 00S UCP Warm 30 00S 6 4 7 Observe the DUT Temperature and Total Historical Regenerative Power This series instrument supports measuring DUT temperature and t...

Page 116: ...ormation are as follows 1 Press composite keys Shift P Set System to enter the System menu 2 Rotate the knob to select System Info and press Enter to confirm 3 Rotate the knob and view the system info...

Page 117: ...he power statistics information when the battery test mode or battery simulation mode is turned on the data will also be cleared Reset Meas The zero clearing operation when the instrument is re powere...

Page 118: ...atus The UUT Over Temperature displayed in front panel is cleared and the instrument exits OCP status 6 7 Sense abnormal protection function When the Remote Measure Function Sense Function is enabled...

Page 119: ...appears and the instrument ex its the Sense abnormal protection status 6 8 Over Temperature Protection An Over Temp Protect will occur if The internal temperature of the instrument exceeds 85 degrees...

Page 120: ...ge that is 20 higher than specified value Otherwise it would damage the instrument For example during setting of voltage or current the input voltage cannot exceed 12V Otherwise it would damage the in...

Page 121: ...the low voltage limit V_low value between 0 and full scale Under the load mode Set the voltage and input 0 10V voltage value to set the input voltage between 0 and full scale 3 6 AGND Ground ing of an...

Page 122: ...al 14 Vol_MON Analog output Monitor the voltage and output 0 10V voltage value to monitor the DC terminal voltage between 0 and full scale 15 Cur_Pro Analog input Under the source mode set current The...

Page 123: ...ale Under the load mode the terminal is controlled by current setting Input 0 10V voltage value to set the input cur rent between 0 and full scale 18 Vref Analog output The 10V reference voltage outpu...

Page 124: ...on the exter nal analog interface function please confirm whether pins 1 Vol_Pro 15 Cur_Pro and 17 Cur Vol_Pro are correctly connected 5 Press Esc key and exit the menu interface Analog interface remo...

Page 125: ...setting I_Lim Connect an external DC power supply capable of outputting 0V 10V between pin 17 Cur Vol_Pro and pin 3 4 5 6 AGND of the analog interface Negative current limit setting I_Lim Connect an...

Page 126: ...is input the instrument s On Off state is switched to On state Voltage and current monitoring Through the analog interface the existing output voltage current or input voltage current can be monitore...

Page 127: ...o current setting pin 17 Cur Vol_Pro and ground wire 3 4 5 6 AGND Oth er analog input pins should also be connected correctly The wiring method is shown in the figure below 6 10 Anti reverse connectio...

Page 128: ...Isolated from the wiring of the energy storage DUT Surge suppress Sense reverse connection protection The dimension figure of the IT E118 anti reverse connection module is as follows Wiring method In...

Page 129: ...e instrument output cannot be turned on When the user enters the battery charge discharge mode Function Bat tery the instrument automatically sets the anti reverse connection module SDS in the system...

Page 130: ...battery test mode Surge Suppress Done The prompt is given when the surge suppress opera tion is succeeded Surge Suppress Fail The prompt is given when the surge suppress opera tion is failed Error Mod...

Page 131: ...in each System Bus link Multi channel systems can be composed of single units of the same series and different models Synchr onizatio n By operating one unit in the System Bus link locally or remotel...

Page 132: ...nection with system bus The cost of the communication cards is saved and the connection interface on the PC side is also reduced When using the multi channel function the instruments in the channels d...

Page 133: ...scribe the connection and operation steps of multiple channels The procedures to set the multiple channels are as follows 1 Set the channel number for each instrument a Press the Shift P set System co...

Page 134: ...Off Only set multiple units to output on off and Save Recall synchronization Track besides output on off and Save Recall synchronization you can set the voltage proportional relation Reference among...

Page 135: ...pressing about 3 s Link key can display the current synchronization status of the instrument At this time pressing Enter key can enter into the synchronization menu setting interface You can set para...

Page 136: ...b Use left and right keys or rotate the knob to select Link and press Enter key to make the parameter in modification c Rotate the knob to set Status and press Enter key to confirm Online indicates t...

Page 137: ...the master unit Each parallel system group supports up to four single units 1 master and 3 slaves for parallel connection Each system bus link can connect up to 16 single units and support up to 16 pa...

Page 138: ...and right keys or rotate the knob to select Parallel and press Enter key to make the parameter in modification c Rotate the knob to select Master and press Enter key to confirm d Set Master group to A...

Page 139: ...and two slave units Group B C one master unit and one slave unit The detailed connection method and procedures are as follows 1 Configure the channel number of each instrument Please refer to 7 1 Mult...

Page 140: ...Slave group to B and C 5 After making the master slave setting the instrument will automatically restart to ensure normal operation Multi Master can compose Multi Channel system for detailed informati...

Page 141: ...d TST If the return value is 0 the self test passes if it is 1 the self test fails If the self test fails please send command SYSTem ERRor to view the self test error Please refer to IT M3600 Programm...

Page 142: ...tioning and measurement during measurement and use Prompt Message List Prompt information Invailid in Source Mode Invalid in CV CC Invalid in CV CR Invalid in CC CR Invalid in BATT SIM Waiting for Tri...

Page 143: ...rument complies with warranty service conditions If after your warranty expires ITECH offers repair services at competitive prices Self inspection of equipment faults When the instrument fails make th...

Page 144: ...ystem Info and press Enter key 3 Use left and right keys or knob to view the SN number Please record the SN number and provide SN information when doing maintenance service How to contact ITECH engine...

Page 145: ...ments and always insure shipments To ship the unit to ITECH for service or repair 1 Download the ITECH maintenance service application from our website complete it and place it in the box with the ins...

Page 146: ...633 IT M3614 IT M3624 IT M3634 IT M3615 IT M3625 IT M3635 10 1 IT M3612 Source Mode Source Parameter Rated value 0 40 Output Voltage 0 60V Output Current 30A 30A Output Power 200W 200W Min operating v...

Page 147: ...Accuracy 1 Pmax Temperature Coefficient Temperature Coefficient Voltage Temperature Coefficient 100ppm Current Temperature Coefficient 50ppm Battery Test AH Measurement AH Range 0AH 300AH Accuracy 0 2...

Page 148: ...tage range 100VAC 240VAC OVP 264VAC UVP 90VAC Frequency 47Hz 63Hz Max current rms 1Aac AC220V DC Offset 0 1A 0 1A Environment Working temperature 0 40 C Storage temperature 20 70 Noise 60dB External t...

Page 149: ...y 1 Rmin 2 0 04 60 1 Rmin 5 60 600 CP Range 0 200W Setup Resolution 0 1W Accuracy 1 0 Pmax Dynamic mode Rising slope 30A ms Falling slope 30A ms Min rise time 1ms Input Read back Read back current Ran...

Page 150: ...30A Current monitoring External 0V 10V is 0 30A Voltage programming External 0V 10V is 0 60V Voltage monitoring External 0V 10V is 0 60V Calculation method of resistance precision range in load mode...

Page 151: ...ck Read back current Range 30A 30A Resolution 1mA Accuracy 0 1 0 1 FS Read back Voltage Range 0 60V Resolution 1mV Accuracy 0 1 Umax Read back Power Range 400W 400W Resolution 0 1W Accuracy 1 Pmax Tem...

Page 152: ...0V 10V is 0 60V Voltage monitoring External 0V 10V is 0 60V Current programming External 10V 10V is 30A 30A Current monitoring External 10V 10V is 30A 30A AC parameters Voltage range 100VAC 240VAC OV...

Page 153: ...t 30A CC Range 0 30A Setup Resolution 10mA Accuracy 0 1 0 1 FS CV Range 0 60V Setup Resolution 1mV Accuracy 0 1 Umax CR Range 0 04 600 Resolution Min 0 001 Accuracy 1 Rmin 2 0 04 60 1 Rmin 5 60 600 CP...

Page 154: ...300AH Accuracy 0 20 Resolution 0 001AH Protection range OCP 31A OVP 61V OPP 410W Short circuit test Current 33A External analog optional Current programming External 0V 10V is 0 30A Current monitorin...

Page 155: ...weight 5kg Calculation method of resistance precision range in load mode lower limit 1 1 R 1 R 0 05 0 004 Upper limit 1 1 R 1 R 0 05 0 004 10 3 IT M3632 Source Mode Parameter IT M3632 V1 2 Rated value...

Page 156: ...tion 1mV Accuracy 0 1 Umax Read back Power Range 800W 800W Resolution 0 1W Accuracy 1 Pmax Temperature Coefficient Temperature Coefficient Voltage Temperature Coefficient 100ppm Current Temperature Co...

Page 157: ...30A Current monitoring External 10V 10V is 30A 30A AC parameters Voltage range 100VAC 240VAC OVP 264VAC UVP 90VAC Frequency 47Hz 63Hz Max current rms 4Aac AC220V Power factor PF 0 98 Lead or Lag DC O...

Page 158: ...FS CV Range 0 60V Setup Resolution 1mV Accuracy 0 1 Umax CR Range 0 04 600 Resolution Min 0 001 Accuracy 1 Rmin 2 0 04 60 1 Rmin 5 60 600 CP Range 0 800W Setup Resolution 0 1W Accuracy 1 0 Pmax Dynam...

Page 159: ...nge OCP 31A OVP 61V OPP 810W Short circuit test Current 33A External analog optional Current programming External 0V 10V is 0 30A Current monitoring External 0V 10V is 0 30A Voltage programming Extern...

Page 160: ...ion method of resistance precision range in load mode lower limit 1 1 R 1 R 0 05 0 004 Upper limit 1 1 R 1 R 0 05 0 004 10 4 IT M3613 Source Mode Parameter IT3613 V1 2 Rated value 0 40 Output Voltage...

Page 161: ...00W Resolution 0 1W Accuracy 1 Pmax Temperature Coefficient Temperature Coefficient Voltage Temperature Coefficient 100ppm Current Temperature Coefficient 50ppm Regulation Load Regulation Voltage 0 05...

Page 162: ...VAC OVP 264VAC UVP 90VAC Frequency 47Hz 63Hz Max current rms 1Aac AC220 DC Offset 0 1A 0 1A Environment Working temperature 0 40 C Storage temperature 20 70 Noise 60dB External temperature measurement...

Page 163: ...1 Rmin 2 0 25 100 1 Rmin 5 100 1500 CP Range 0 200W Setup Resolution 0 1W Accuracy 1 0 Pmax Dynamic mode Rising slope 12A ms Falling slope 12A ms Min rise time 1ms Input Read back Read back current R...

Page 164: ...oltage monitoring External 0V 10V is 0 150V Calculation method of resistance precision range in load mode lower limit 1 1 R 1 R 0 05 0 004 Upper limit 1 1 R 1 R 0 05 0 004 10 5 IT M3623 Source Mode Pa...

Page 165: ...tion 10mV Accuracy 0 1 Umax Read back Power Range 400W 400W Resolution 0 1W Accuracy 1 Pmax Temperature Coefficient Temperature Coefficient Voltage Temperature Coefficient 100ppm Current Temperature C...

Page 166: ...parameters Voltage range 100VAC 240VAC OVP 264VAC UVP 90VAC Frequency 47Hz 63Hz Max current rms 2Aac AC220 DC Offset 0 1A 0 1A Environment Working temperature 0 40 C Storage temperature 20 70 Noise 60...

Page 167: ...Min 0 01 Accuracy 1 Rmin 2 0 25 100 1 Rmin 5 100 1500 CP Range 0 400W Setup Resolution 0 1W Accuracy 1 0 Pmax Dynamic mode Rising slope 12A ms Falling slope 12A ms Min rise time 1ms Input Read back Re...

Page 168: ...ernal 0V 10V is 0 150V Voltage monitoring External 0V 10V is 0 150V AC parameters Voltage range 100VAC 240VAC OVP 264VAC UVP 90VAC Frequency 47Hz 63Hz Max current rms 2Aac AC220 DC Offset 0 1A 0 1A En...

Page 169: ...Min operating voltage 15V at 12A CC Range 12A 12A Setup Resolution 1mA Accuracy 0 1 0 1 FS CV Range 0 150V Setup Resolution 10mV Accuracy 0 1 Umax Internal Resistance CV Prior ity mode Range 0 1000m S...

Page 170: ...0 05 Imax Ripple Ripple Voltage 300mVp p Current 30mArms value voltage rise fall time Rise time Voltage No load 20ms Rise time Voltage Full load 50ms Fall time Voltage No load 20ms Fall time Voltage...

Page 171: ...range 20 120 Measurement accuracy 1 Measurement resolution 0 1 Efficiency Max efficiency Full load 88 Communication Optional Communication interfaces RS232 USB RS485 CAN LAN GPIB Analog Mechanical par...

Page 172: ...0 12A Resolution 1mA Accuracy 0 1 0 1 FS Read back Voltage Range 0 150V Resolution 10mV Accuracy 0 1 Umax Read back Resistance Range 0 25 1500 Resolution 0 01 Accuracy 1 Rmin 2 0 25 100 1 Rmin 5 100...

Page 173: ...HDI 5 Environment Working temperature 0 40 C Storage temperature 20 70 Noise 60dB External temperature measurement Measurement range 20 120 Measurement accuracy 1 Measurement resolution 0 1 Efficiency...

Page 174: ...2 Rmax CP Range 200W 200W Setup Resolution 0 1W Accuracy 1 0 Pmax CR mode CC Priority mode Range 5 1000 Resolution Min 0 1 Accuracy Rmin Vreal Vmax 0 1 Rset Imax 0 2 Rmax Vreal Vmax 0 1 Rset Imax 0 2...

Page 175: ...ent Response Time Voltage 2mS Output Protection range OCP 6 2A or 6 2A OVP 305V OPP 210W or 210W External analog optional Voltage programming External 0V 10V is 0 300V Voltage monitoring External 0V 1...

Page 176: ...weight 5kg Load Mode Parameter IT M3614 V1 2 Load Parameter Rated value 0 40 Input Voltage 0 300V Input Current 0 6A Input Power 0 200W Min operating voltage 5V at 6A CC Range 0 6A Setup Resolution 1m...

Page 177: ...ure Coefficient Voltage Temperature Coefficient 100ppm Current Temperature Coefficient 50ppm Protection range OCP 6 2A OVP 310V OPP 210W Short circuit test Current 6 6A External analog optional Curren...

Page 178: ...Size and weight 450mm 214mm 43 5mm Net weight 5kg Calculation method of resistance precision range in load mode lower limit 1 1 R 1 R 0 05 0 004 Upper limit 1 1 R 1 R 0 05 0 004 10 8 IT M3624 Source...

Page 179: ...acy 0 1 0 1 FS Read back Voltage Range 0 300V Resolution 10mV Accuracy 0 1 Umax Read back Power Range 400W 400W Resolution 0 1W Accuracy 1 Pmax Temperature Coefficient Temperature Coefficient Voltage...

Page 180: ...xternal 10V 10V is 6A 6A AC parameters Voltage range 100VAC 240VAC OVP 264VAC UVP 90VAC Frequency 47Hz 63Hz Max current rms 2Aac AC220V DC Offset 0 1A 0 1A Environment Working temperature 0 40 C Stora...

Page 181: ...0 Resolution Min 1 Accuracy 1 Rmin 2 1 300 1 Rmin 5 300 3000 CP Range 0 400W Setup Resolution 0 1W Accuracy 1 0 Pmax Dynamic mode Rising slope 6A ms Falling slope 6A ms Min rise time 1ms Input Read ba...

Page 182: ...programming External 0V 10V is 0 300V Voltage monitoring External 0V 10V is 0 300V AC parameters Voltage range 100VAC 240VAC OVP 264VAC UVP 90VAC Frequency 47Hz 63Hz Max current rms 2Aac AC220V DC Of...

Page 183: ...Output Power 800W 800W Min operating voltage 30V at 6A CC Range 6A 6A Setup Resolution 1mA Accuracy 0 1 0 1 FS CV Range 0 300V Setup Resolution 10mV Accuracy 0 1 Umax Internal Resistance CV Prior ity...

Page 184: ...ge 0 05 Umax Current 0 05 Imax Ripple Ripple Voltage 600mVp p Current 30mArms value voltage rise fall time Rise time Voltage No load 20ms Rise time Voltage Full load 50ms Fall time Voltage No load 20m...

Page 185: ...20 120 Measurement accuracy 1 Measurement resolution 0 1 Efficiency Max efficiency Full load 88 Communication Optional Communication interfaces RS232 USB RS485 CAN LAN GPIB Analog Mechanical paramete...

Page 186: ...nge 0 300V Resolution 10mV Accuracy 0 1 Umax Read back Resistance Range 1 3000 Resolution 1 Accuracy 1 Rmin 2 1 300 1 Rmin 5 300 3000 Read back Power Range 0 800W Resolution 0 1W Accuracy 1 Pmax Tempe...

Page 187: ...temperature 20 70 Noise 60dB External temperature measurement Measurement range 20 120 Measurement accuracy 1 Measurement resolution 0 1 Efficiency Max efficiency Full load 88 Communication Optional...

Page 188: ...Input Read back Read back current Range 0 6A Resolution 0 1mA Accuracy 0 1 0 1 FS Read back Voltage Range 0 300V Resolution 10mV Accuracy 0 1 Umax Read back Resistance Range 1 3000 Resolution 1 Accura...

Page 189: ...g DC Offset 0 1A 0 1A Harmonic THDI 5 Environment Working temperature 0 40 C Storage temperature 20 70 Noise 60dB External temperature measurement Measurement range 20 120 Measurement accuracy 1 Measu...

Page 190: ...Resistance CV Prior ity mode Range 0 1000m Setup Resolution 0 1m Accuracy 2 Rmax CP Range 200W 200W Setup Resolution 0 1W Accuracy 1 0 Pmax CR mode CC Priority mode Range 20 1000 Resolution Min 0 1 A...

Page 191: ...se time Voltage Full load 60ms Fall time Voltage No load 30ms Fall time Voltage Full load 30ms Transient Response Time Voltage 2mS Output Protection range OCP 3 1A or 3 1A OVP 610V OPP 210W or 210W Ex...

Page 192: ...USB RS485 CAN LAN GPIB Analog Mechanical parameters Size and weight 450mm 214mm 43 5mm Net weight 5kg Load Mode Parameter IT M3615 V1 2 Load Parameter Rated value 0 40 Input Voltage 0 600V Input Curr...

Page 193: ...n 5 600 6000 Read back Power Range 0 200W Resolution 0 1W Accuracy 1 Pmax Temperature Coefficient Temperature Coefficient Voltage Temperature Coefficient 100ppm Current Temperature Coefficient 50ppm P...

Page 194: ...load 88 Communication Optional Communication interfaces RS232 USB RS485 CAN LAN GPIB Analog Mechanical parameters Size and weight 450mm 214mm 43 5mm Net weight 5kg Calculation method of resistance pre...

Page 195: ...ax 0 2 Rmax Vreal Vmax 0 1 Rset Imax 0 2 Output Read back Read back current Range 3A 3A Resolution 0 1mA Accuracy 0 1 0 1 FS Read back Voltage Range 0 600V Resolution 10mV Accuracy 0 1 Umax Read back...

Page 196: ...is 0 600V Voltage monitoring External 0V 10V is 0 600V Current programming External 10V 10V is 3A 3A Current monitoring External 10V 10V is 3A 3A AC parameters Voltage range 100VAC 240VAC OVP 264VAC U...

Page 197: ...0 3A Setup Resolution 1mA Accuracy 0 1 0 1 FS CV Range 0 600V Setup Resolution 10mV Accuracy 0 1 Umax CR Range 4 6000 Resolution Min 1 Accuracy 1 Rmin 2 4 600 1 Rmin 5 600 6000 CP Range 0 400W Setup...

Page 198: ...og optional Current programming External 0V 10V is 0 3A Current monitoring External 0V 10V is 0 3A Voltage programming External 0V 10V is 0 600V Voltage monitoring External 0V 10V is 0 600V AC paramet...

Page 199: ...M3635 V1 2 Source Parameter Rated value 0 40 Output Voltage 0 600V Output Current 3A 3A Output Power 800W 800W Min operating voltage 60V at 3A CC Range 3A 3A Setup Resolution 1mA Accuracy 0 1 0 1 FS C...

Page 200: ...fficient 50ppm Regulation Load Regulation Voltage 0 05 Umax Current 0 05 Imax Line Regulation Voltage 0 05 Umax Current 0 05 Imax Ripple Ripple Voltage 1200mVp p Current 30mArms value voltage rise fal...

Page 201: ...c THDI 5 Environment Working temperature 0 40 C Storage temperature 20 70 Noise 60dB External temperature measurement Measurement range 20 120 Measurement accuracy 1 Measurement resolution 0 1 Efficie...

Page 202: ...sing slope 3A ms Falling slope 3A ms Min rise time 1ms Input Read back Read back current Range 0 3A Resolution 0 1mA Accuracy 0 1 0 1 FS Read back Voltage Range 0 600V Resolution 10mV Accuracy 0 1 Uma...

Page 203: ...P 90VAC Frequency 47Hz 63Hz Max current rms 4Aac AC220V Power factor PF 0 98 Lead or Lag DC Offset 0 1A 0 1A Harmonic THDI 5 Environment Working temperature 0 40 C Storage temperature 20 70 Noise 60dB...

Page 204: ...Technical Specification Calculation method of resistance precision range in load mode lower limit 1 1 R 1 R 0 05 0 004 Upper limit 1 1 R 1 R 0 05 0 004 Copyright Itech Electronic Co Ltd 192...

Page 205: ...Supplemental Characteristics 11 Supplemental Characteristics Recommended calibration frequency once a year Cooling style fans Copyright Itech Electronic Co Ltd 193...

Page 206: ...end and a banana plug at the other end IT E30110 BB 10A 1m A pair of red and black test ca bles with banana plugs at both ends IT E30110 BY 10A 1m A pair of red and black test ca bles with a banana pl...

Page 207: ...5 3 5 2 5 1 7 AWG American Wire Gage it means X wire marked on the wire The table above lists current capacity of single wire at working temperature of 30 C For reference only Along with temperature y...

Page 208: ...tact Us Thanks for purchasing ITECH products In case of any doubts please con tact us as follows 1 Visit ITECH website www itechate com 2 Select the most convenient contact method for further informat...