IPBridge Installation Guide
Page 8
2: PHYSICAL INSTALLATION
When selecting the location where you are going to mount the ISONAS IP-Bridge,
a few guidelines should be observed.
1)
The IP-Bridge should be protected from extreme heat and sunlight. It is
rated for indoor use, between -40 to 80 degrees C.
2)
The IP-Bridge is designed to be mounted on a standard 35 mm DIN Rail.
3)
Mounting the IP-Bridge inside of a control cabinet or a NEMA housing
is recommended.
4)
When planning a project’s DIN rail layout, determine if the door device’s
electrical return connections will be terminated by the optional modular DIN
terminal blocks. If so, adjust the IP-Bridge’s location on the DIN rail to
allow space for the modular terminal blocks.
5)
The IP-Bridge should be located within a 500 foot cable length of the devices
being controlled.
2.1
: MOUNTING THE IP-BRIDGE
The major steps involved with the physical mounting of the IP-Bridge include:
1)
Planning the location of the DIN rail(s)
a.
Typically inside a control cabinet, or NEMA housing.
2)
Attaching the DIN rails to housing’s mounting surface
3)
Snapping the IP-Bridge to its DIN rail
4)
Attaching the optional terminal block(s)
5)
Repeat the process, for any additional IP-Bridges