Module Input
Results
TO Switch
Priority Array
Present Value
Digital Output
Status Flag Property
Auto position
NULL
Default
Default
0000
DUTY VALUE
DUTY VALUE
ON/OFF
Manual position
ON
NULL
100%
ON
0010
DUTY VALUE
Manual position
OFF
NULL
0%
OFF
0010
DUTY VALUE
Table 29. Status Flag property changes
8.5.3 HAND_STATUS Object (Multistate Value: 23-26)
The Hand Status object stores the status of the hand operation switch and the status of
the TO in the hand mode according to the table below:
Value of Hand Status
Status Description
1
AUTO-OUT=OFF
2
AUTO-OUT=ON
3
HAND-OUT=OFF
4
HAND-OUT=ON
Table 30. The Hand Status object value list
8.5.4 TO CONFIGURATION Object (Multistate Value: 17-22)
This object contains information about the mode of the triac output according to the
following table:
Property Value
Description
1 (default)
Digital Output
2
PWM 1 Hz
3
PWM 10 Hz
4
PWM 0.1 HZ
5
PWM 0.01Hz
Table 31. The TO Configuration object value list